KACO Powador XP500-XP550-HV TL User Manual
Page 53
Operating Instructions Powador XP500/550-HV-TL
Page 53
Faults and Warnings
Code Message
Warning Description
Possible problem and Solution(s)
33
Grid Under Frequency
level 1
Grid side Frequency under the
parameter [Grid Under Fre-
quency Level 1]
Possible problem
• The grid frequency is outside the
operation range
Solution(s)
• Check the grid frequency
• Check the grid parameter
34
Grid CB Trip
CB20(AC Disconnect/Grid circuit
breaker) was tripped during
operation
Possible problem
• Short circuit in the grid
Solution(s)
• Check the wiring connections
35
Grid Over Voltage
Level 2
Grid side Voltage over the
parameter [Grid Over Voltage
Level 2]
Possible problem
• The grid voltage is too high
Solution(s)
• Check the grid voltage
• Check the grid parameter
36
Grid Under Voltage
Level 2
Grid side Voltage Under the
parameter [Grid Under Voltage
Level 2]
Possible problem
• The grid voltage is too low
Solution(s)
• Check the grid voltage
• Check the grid parameter
37
Grid Under Frequency
Level 2
Grid side Frequency Under the
parameter [Grid Under Fre-
quency Level 2]
Possible problem
• The grid frequency is outside the
operation range
Solution(s)
• Check the grid frequency
38
Grid Over Frequency
Level 2
Grid side Frequency Over the
parameter [Grid Over Frequency
Level 2]
Possible problem
• The grid frequency is outside the
permitted range
Solution(s)
• Check the grid frequency
40
Parameters
Version Error
Different version between the
NVSRAM parameter table and
the program parameter table
Possible problem
• Different version between the NVSRAM
parameter table and the program
parameter table
Solution(s)
• Initialize the parameter menu setting in
the GUI and reset faulted parameter
• Change the PCB module
Table 10: Fault