Faults and Warnings

Code Message

Warning Description

Possible problem and Solution(s)

33

Grid Under Frequency
level 1

Grid side Frequency under the
parameter [Grid Under Fre-
quency Level 1]

Possible problem
• The grid frequency is outside the
operation range
Solution(s)
• Check the grid frequency
• Check the grid parameter

34

Grid CB Trip

CB20(AC Disconnect/Grid circuit
breaker) was tripped during
operation

Possible problem
• Short circuit in the grid
Solution(s)
• Check the wiring connections

35

Grid Over Voltage
Level 2

Grid side Voltage over the
parameter [Grid Over Voltage
Level 2]

Possible problem
• The grid voltage is too high
Solution(s)
• Check the grid voltage
• Check the grid parameter

36

Grid Under Voltage
Level 2

Grid side Voltage Under the
parameter [Grid Under Voltage
Level 2]

Possible problem
• The grid voltage is too low
Solution(s)
• Check the grid voltage
• Check the grid parameter

37

Grid Under Frequency
Level 2

Grid side Frequency Under the
parameter [Grid Under Fre-
quency Level 2]

Possible problem
• The grid frequency is outside the
operation range
Solution(s)
• Check the grid frequency

38

Grid Over Frequency
Level 2

Grid side Frequency Over the
parameter [Grid Over Frequency
Level 2]

Possible problem
• The grid frequency is outside the
permitted range
Solution(s)
• Check the grid frequency

40

Parameters
Version Error

Different version between the
NVSRAM parameter table and
the program parameter table

Possible problem
• Different version between the NVSRAM
parameter table and the program
parameter table
Solution(s)
• Initialize the parameter menu setting in
the GUI and reset faulted parameter
• Change the PCB module

Table 10: Fault