3 solution for error code – KACO Powador XP500-XP550-HV TL User Manual
Page 48
Page 48
Operating Instructions Powador XP500/550-HV-TL
Faults and Warnings
6.3 Solution for Error code
The Inverter can detect faults during operation. The inverter will display the fault in the GUI. Faults are indicated
in the GUI with an error code, and a plain text message with the error code and system plant name in the text
line will be sent to the system operator (only available if purchased and configured during setup). This section
describes how to recognize the types of faults and how to correct these faults.
Warning
Code Message
Warning description
Possible problem and Solution(s)
81
SP1(PV SP) Failure
Failure of the PV side surge
protector(SP1)
Possible problem
• Lightning strike on or near the PV system
wiring
Solution(s)
• Visual inspection
• Change the SPD
83
PV Fuse Failure
PV side Fuse failure(option)
Possible problem
• PV system wiring short
• Short circuit in the IGBT
Solution(s)
• Check the input current
• Check module wiring
• Change the FUSE
100
PEBB Over Temp.
Warning
The temperature of the
PEBB(Power Electronics Building
Block) over 85°C(185°F)
Possible problem
• PEBB Fan Failure
Solution(s)
• Clean the filters or PEBB heat-sink fins
• Change the PEBB Fan
101
PEBB Fan Failure
Failure of a PEBB(Power Elec-
tronics Building Block) fan
Possible problem
• PEBB Fan Failure
Solution(s)
• Change the PEBB Fan
110
SP2(Grid SP) Failure
Failure of the grid side surge
protector(SP2)
Possible problem
• Lightning strike on or near the grid
system wiring
Solution(s)
• Visual inspection
• Change the SPD
120
Test Mode
The system is working in test
mode
Possible problem
• The system is working in test mode
Solution(s)
• Change the parameters in the GUI
Table 9: Warning