Faults and Warnings
Message
Code
Description
Grid Under Voltage 1
31
Grid side Voltage under the parameter [Grid Under Voltage Level 1]
Grid Over Frequency 1
32
Grid side Frequency over the parameter [Grid Over Frequency Level 1]
Grid Under Frequency 1
33
Grid side Frequency under the parameter [Grid Under Frequency Level 1]
Grid CB Trip
34
CB20(AC Disconnect/Grid circuit breaker) was tripped during operation
Grid Over Voltage 2
35
Grid side Voltage over the parameter [Grid Over Voltage Level 2]
Grid Under Voltage 2
36
Grid side Voltage Under the parameter [Grid Under Voltage Level 2]
Grid Under Frequency 2
37
Grid side Frequency Under the parameter [Grid Under Frequency Level 2]
Grid Over Frequency 2
38
Grid side Frequency Over the parameter [Grid Over Frequency Level 2]
Parameters Version Error
40
Different version between the NVSRAM parameter table and the pro-
gram parameter table
Flash Memory Failure
41
C6000 DSP program flash memory failure in XCU(main control) board
FPGA Failure
42
FPGA failure in XCU(main control) board
DSP28x Failure
43
F2000 DSP failure in XCU(main control) board
ADC Failure
44
ADC block failure in XCU(main control) board
NVSRAM Failure
45
NVSRAM Failure in XCU(main control) board or invalid parameter set-
ting
Asynchronous
46
Synchronous fail of Grid and Inverter
CAN Failure
47
CAN bus communication failure
Emergency Stop
50
A door is open
MasterSlave Fault
52
Master Slave operation Failure
Grid Over Frequency Level3 57
Grid side Frequency over the parameter [Grid Over Frequency Level 3]
Grid Under Frequency
Level3
58
Grid side Frequency under the parameter [Grid Under Frequency Level 3]
Grid Over Voltage Slow
59
Grid side Voltage over the parameter [Grid Over Voltage Level Slow]
(RMS average value per 10 min)
MMI-XCU Communication
Error
63
MMI-XCU communication Error
Table 8: Fault