KACO Powador XP500-XP550-HV TL User Manual

Page 90

background image

Page 90

Operating Instructions Powador XP500/550-HV-TL

User interface

The system sends digital input signal in accordance with the setting of “DI1 Select” parameter in menu of MMI
or parameter setup tool (CMT, AutoSetup).

DI1 Select

Description

Note

0

Disable DI1

1

Reserved

2

Reserved

3

Start/Stop operation of the inverter by DI1

Recognition pattern:

Stop: ∆t = 1sec

Start: ∆t = 2sec

Recognition pattern is checked whene-

ver DI1 input signal is at rising edge(T

0

)

then it is determined according to how
long the DI1 input signal has been
stayed in high state.

4

Start/Stop operation of the inverter by DI1

Recognition pattern:

Stop: ∆t = 200msec

Start: ∆t = 400msec

5

Stop operation of the inverter by DI1

Recognition pattern:

{DI1 Check Period} msec – Stop operation

Figure 77: DI1 input signal

NOTE

The {DI1 Check Period} is parameter in ‘8.5 Digital Parameters’ that mean recognition pattern
period for inverter stop operation when selecting ‘DI1 Select’ to ‘5’.