Operating Instructions Powador XP500/550-HV-TL
User interface
The system sends digital input signal in accordance with the setting of “DI1 Select” parameter in menu of MMI
or parameter setup tool (CMT, AutoSetup).
DI1 Select
Description
Note
0
Disable DI1
1
Reserved
2
Reserved
3
Start/Stop operation of the inverter by DI1
Recognition pattern:
Stop: ∆t = 1sec
Start: ∆t = 2sec
Recognition pattern is checked whene-
ver DI1 input signal is at rising edge(T
0
)
then it is determined according to how
long the DI1 input signal has been
stayed in high state.
4
Start/Stop operation of the inverter by DI1
Recognition pattern:
Stop: ∆t = 200msec
Start: ∆t = 400msec
5
Stop operation of the inverter by DI1
Recognition pattern:
{DI1 Check Period} msec – Stop operation
Figure 77: DI1 input signal
NOTE
The {DI1 Check Period} is parameter in ‘8.5 Digital Parameters’ that mean recognition pattern
period for inverter stop operation when selecting ‘DI1 Select’ to ‘5’.