Operating Instructions Powador XP500/550-HV-TL
Storage/Installation/Start-up
5.4.2 Protective earth connection
Connect the PE bus bars
The PE (protective earth) bus bars are located on the left and right sides of the inverter cabinets.
"
Connect the wires for “both” PE bus bars.
Earth the inverter
"
Determine the lay-out of the permanent wiring.
"
Secure the protective earths (tightening torque for PE terminals: 25Nm). Do not use plug connections.
"
Check whether all connected cables are securely attached and protected from mechanical forces.
"
Attach the Plexiglas cover.
Figure 9: PE busbar