Operating Instructions Powador XP500/550-HV-TL

Storage/Installation/Start-up

5.4.2 Protective earth connection

Connect the PE bus bars
The PE (protective earth) bus bars are located on the left and right sides of the inverter cabinets.

"

Connect the wires for “both” PE bus bars.

Earth the inverter

"

Determine the lay-out of the permanent wiring.

"

Secure the protective earths (tightening torque for PE terminals: 25Nm). Do not use plug connections.

"

Check whether all connected cables are securely attached and protected from mechanical forces.

"

Attach the Plexiglas cover.

Figure 9: PE busbar