3 frequency dependant power reduction enable on, Grid under voltage, Grid over frequency – KACO Powador XP500-XP550-HV TL User Manual

Page 68

background image

Page 68

Operating Instructions Powador XP500/550-HV-TL

Parameters

Grid Under Voltage

Figure 52: Grid under voltage

1. U > 1.1*U

rated

, t > 2s → Grid Under Voltage Level 1 Fault

2. U > 1.2*U

rated

, t > 150ms → Grid Under Voltage Level 2 Fault

8.3.3 Frequency Dependant Power Reduction Enable On

Grid Over Frequency

Figure 53: Grid over frequency