Parameters
8
Parameters
The KACO XP-HV and XP-TL series parameters are pre-configured for operation. It is a good idea to adapt a
number of the KACO XP series parameters to the solar generator.
The KACO XP-HV and XP-TL series parameters are subdivided into ten:
• PV Array
Setting values for MPPT control and startup of inverter
• Inverter
Setting values for inverter rate and cabinet temperature
• Grid
Setting values for abnormal and rated levels of grid
• Time
Setting values for the current time
• Digital
Setting values for digital interface
• Analog
Setting values for analog interface
• Controller
Setting values for inverter control
• Trace
Setting values for inverter fault analysis
• Offset
Setting values for sensing offset calibration
• Gain
Setting values for sensing gain calibration
8.1 PV Array Parameters
Parameters
Min
Max
Unit
Descriptions
MPPT Enable
0
1
-
1: MPPT is enabled
0: MPPT is disabled
MPPT V Maximum
0
830
V
dc
Maximum voltage to run MPPT
MPPT V Start
200
800
V
dc
MPPT wake-up voltage
MPPT T Start
0
3600
sec
Time delay for MPPT wake-up
MPPT P Stop
0
10000
W
Disconnect inverter from Grid when PV output
power is lower than the setting value of {MPPT P
Stop}.
MPPT T Stop
0
600
sec
Time delay while inverter decides if PV output
power is lower than the setting value of {MPPT P
Stop}.
Table 12: PV Array Parameters