background image

6 - 30

YASNAC PCNC PLC Programming Manual Chapter 6: PLC Instructions

(20)CPR (Compare Register) RR after operation: RR-

a) Function

The instruction executes comparison between R1 and R2 when the ST contact
is ON (RR = 1), and sets “0” or “1” to Z1 according to the result of comparison.

R1 < R2 Z1 = 0

R1

R2 Z1 = 1

If the ST contact is OFF (RR = 0), the CPR instruction is not executed.The content
of RR remains at “0”.

(b) Format

(c) Explanation

After the execution of the CPR instruction, the contents of R1 and R2 remain
unchanged.

An ST contact must be entered before the CPR instruction.

The CPR instruction is executed in intervals of “4 × n” msec while the ST contact
is ON.

(d) Example

(21)COR (Coincide Register) RR after operation: RR-

(a) Function

The instruction executes comparison between R1 and R2 when the ST contact is ON
(RR = 1), and sets “0” or “1” to Z1 according to the result of comparison.

R1 = R2 Z1 = 0

R1

R2 Z1 = 1

If the ST contact is OFF (RR = 0), the COR instruction is not executed. The content of
RR remains unchanged.