beautypg.com

Yaskawa YASNAC PC NC PLC Programming Manual User Manual

Page 166

background image

8 - 18

YASNAC PCNC PLC Programming Manual Chapter 8: Online Editing

8.4.3

Inputting Contacts

(1) Inputting Contacts

€ When a function

soft-key

presenting a contact is pressed, the message asking the input

of the contact (switch) number is displayed.

Fig. 8.9 Contact Input Screen

ó Input the contact number.
ì The relationship between the contact instruction and the registers that can be input is

indicated below.

:

#1000 to #1063, #1100 to #1175, #1200 to #1299, #1400 to #1699
#1800 to #2999, #3500 to #3699, #7000 to #7999.

:

#1100 to #1163, #1200 to #1299, #1400 to #1699 #1800 to #2999,
#3000 to #3159, #7000 to #7999.

If a contact number which does not correspond to the designated contact instruction is
input, an error occurs and the following warning message is displayed.

“INPUT ERROR”

If this warning message is displayed, check the contact number again and input the correct
one.