6 - 22

YASNAC PCNC PLC Programming Manual Chapter 6: PLC Instructions

(b) Format

(c) Explanation

An ST contact must be entered before the ANI instruction.

The ANI instruction is executed in intervals of “4 × n” msec while the ST contact is
ON.

The relationship between register and numeric value is shown below”.

(d) Example

(8) ORI (OR Immediate) RR after operation: RR-

(a) Function

The instruction executes OR between the specified numeric value and the content of the
register and stores the result to the register when the ST contact is ON (RR = 1). If the
ST contact is OFF (RR = 0), the instruction is not executed.

The RR content remains unchanged before and after the execution of the ORI instruction.

(b) Format

D7

D6

D5

D4

D3

D2

D1

D0

Register

0

0

1

1

0

0

1

1

Numeric value

0

1

0

1

0

1

0

1

Result

0

0

0

1

0

0

0

1