RLE LD2100 V.2.6 User Manual
Page 92

92
LD2100 User Guide
800.518.1519
B
Technical Specifications
SMTP (Email)
Supports Client Authentication (plain and login); compatible
with ESMTP Servers
Modbus EIA-485
Slave; RTU Mode; Supports function codes 03, 04, 06 and 16;
RTU mode for integration with RLE's LD5100, LD2100,
LD2000, and LD1500 products only; Johnson N2
Modbus TCP/IP
Modbus Slave; TCP/IP transmission protocol; TCP/IP
transmission protocol for integration with RLE's LD2100,
LD2000, and LD1500 products only
BACnet/IP
ASHRAE STD 135-2004 Annex J; PICS - protocol
implementation conformance statement
BACnet MS/TP
EIA-485
Terminal Emulation (RS-232)
VT100 compatible
Alarm Notification
Audible Alarm
70dBA @ 2ft (0.6m); re-sound configurable (0-24 hrs., integer)
Visual Alarm
Green, alphanumeric, 8-character dot matrix LED display; bi-
color status LED
Email (Ethernet)
4 Email recipients; email sent on Alarm and Return to Normal;
each alarm notifies all email recipients
SNMP Traps (Ethernet)
4 Community Strings
Logging Capabilities
Event Log
Last 500 events
Trend Log
Cable current level every day, for the last 288 days
Login Security
Web Browser Access (Ethernet)
1 Web password Read Only; 1 Web password Read/Write
Terminal Emulation Access None
Front Panel Interface
Display
Green, alphanumeric, 8-character dot matrix LED display; bi-
color status LED
Push Buttons
Test/Reset: 1
LED Indicators
Power/Status: 1 bi-color (Power On: green; Alarm: red)
Operating Environment
Temperature
32° to 122°F (0° to 50°C)
Humidity
5% to 95% RH, non-condensing
Altitude
15,000ft (4,572m) max.
Storage Environment
-4° to 185°F (-20° to 85°C)
Dimensions
8.0"W x 4.25"H x 1.25"D (203mmW x 108mmH x31.75mmD)
Weight
1.5 lbs. (680g)
Mounting
Wall mountable; wall-mount enclosure LD-ENC or LD-ENC-NP
(optional)
Certifications
CE; ETL listed: conforms to UL STD 61010-1, EN STD
61010-1; certified to CSA C22.2 STD NO. 61010-1; RoHS
compliant
Table B.1 Technical Specifications (continued)