Connect the seahawk leak detection cable – RLE LD2100 V.2.6 User Manual

Page 17

background image

rletech.com

LD2100 User Guide

17

2

Installation

2.5.

Connect the SeaHawk Leak Detection Cable

The LD2100 is shipped with a 15-foot (4.57m) leader cable. Since sensing cable cannot

connect directly to a leak detection controller, one end of this leader cable connects to the

LD2100 controller, and the other end connects to the SeaHawk sensing cable. Connect each

end of the leader cable as follows:

1

With the screws of terminal block connector TB2 on the LD2100 facing up, connect the

four stripped, bare wires of the leader cable to the terminals in this order, from left to right:

white, black, green, red.

Note

If the terminal connector is removed from the end of the cable, make sure the wires are in

this same order when the connector is reapplied.

2

Unscrew the end-of-line (EOL) terminator from the other end of the leader cable.

3

Attach the first length of sensing cable to the leader cable.

4

Route the sensing cable according to a cable layout diagram. Attach additional lengths of

sensing cable as needed.

5

Secure the EOL terminator to the unoccupied end of the sensing cable.

Figure 2.2

Connecting the Sensing Cable

Figure 2.3

SeaHawk Sensing Cable