Controls and displays, Table 2.1, Ld2100 controls and displays – RLE LD2100 V.2.6 User Manual
Page 14
14
LD2100 User Guide
800.518.1519
2
Installation
2.2.
Controls and Displays
The front of the LD2100 contains the following controls and displays:
Item
Description
Digital LED display
•
In a normal operating state, this LED displays the
LD2100
product name with a spinning bar (
|
) to the right of the name.
•
In an alarm state, the LED displays information about the
alarm condition; for example, if a leak is detected, the LED
displays a message with a leak detection cable distance
included. For example:
Leak detected
250 uA
at 675 ft (or 205.74m)
Note: Current range for a leak: 235 – 302 uA
Status LED
Green: The LD2100 is powered on and in a normal operating state.
Red: The LD2100 is in an alarm state.
Test/Reset button
If an alarm is sounding, briefly pressing the button turns off the
audible alarm. The Status LED remains red, and the digital LED
display continues to show the alarm condition.
In an alarm condition, whether the alarm is sounding or not,
pressing and holding this button clears the alarm.
In normal operating conditions, pressing the Reset button
causes the display to cycle through four lines:
LeakageC
nnnn uA
Length
nnn ft (or nnn m)
After a short pause, the LD2100 returns to the default display or
continues to display the alarm, depending on the value entered in
the Re-Alarm Interval field on the Leak Settings web page (see
Table 3.2, “Leak Configuration Options” on page 30 for more
information).
Table 2.1
LD2100 Controls and Displays