5.2. Packet
Communications for the LD2100
This section covers the registers with the name and a brief description of each.
5.2.1 Function 03: Read Output Registers
To read the LD2100 parameter values, the master must send a Read Output Registers request
packet.
The Read Output Registers request packet specifies a start register and the number of registers
to read. The start register is numbered from zero (40001 = zero, 40002 = one, etc).
Table 5.2 Read Output Register Packet Structure
Read Registers Request Packet
Read Registers Response Packet
Slave Address (1 byte)
Slave Address (1 byte)
03 (Function code) (1 byte)
03 (Function code) (1 byte)
Start Register (2 bytes)
Byte count (1 byte)
# of registers to read (2 bytes)
First register (2 bytes)
CRC Checksum (2 bytes)
Second register (2 bytes)
…
Cry Checksum (2 bytes)
Table 5.3 Output Registers
Register
Name
Description
Units
Range
40001
Leak Threshold
Trip current for leak
alarm
25-295 uAmps
0-65535
40002
Contamination
Threshold
Trip current for
contamination alarm
20-295 uAmps
0-65535
40003
Re-Alarm Delay
The time that elapses
between when an alarm
is detected and when it is
annunciated
0-24 Hours
0-65535
40004
Latching Alarms
Designate the alarms as
latching or non-latching
0=No, 1=Yes
0-65535
40005
Silence Audible Alarm
Silence the audible
alarm
1=Silenced
0-65535
40006
Reset Alarms
Reset all the alarms
1=Reset
0-65535
40007
Spare
0-65535
40008
Spare
0-65535
40009
Spare
0-65535
40010
Spare
0-65535