LD2100 User Guide

800.518.1519

3

Web Interface

Set Cable Relay Button - Used to troubleshoot the controller, this button simulates 8060

ohms of leak detection cable (approximately 2878 feet of 2.8 ohms/foot cable) for up to 5

minutes. Push the button and then look at the web interface home page. If the controller is

functioning properly, the cable length will register approximately 2878 feet, and the leg 1

and leg 2 resistance will be approximately 8060 ohms.

Latching Alarms

A non-latching alarm resets itself once a detected leak or

contamination has been resolved.

A latching alarm must be manually acknowledged before its

annunciation clears, even if the detected leak or cable problem is

no longer present.

Select Yes (latching) or No (non-latching).

Default setting: No (non-latching alarms)

Audible Alarm

Select Enabled to activate the audible alarm annunciation. Disable

this option to deactivate the audible alarm annunciation.

Default setting: Disabled

Length Calibration

Factor

Reserved for manufacturer’s use only.

Option

Description