RLE LD2100 V.2.6 User Manual
Page 32

32
LD2100 User Guide
800.518.1519
3
Web Interface
Set Cable Relay Button - Used to troubleshoot the controller, this button simulates 8060
ohms of leak detection cable (approximately 2878 feet of 2.8 ohms/foot cable) for up to 5
minutes. Push the button and then look at the web interface home page. If the controller is
functioning properly, the cable length will register approximately 2878 feet, and the leg 1
and leg 2 resistance will be approximately 8060 ohms.
Latching Alarms
A non-latching alarm resets itself once a detected leak or
contamination has been resolved.
A latching alarm must be manually acknowledged before its
annunciation clears, even if the detected leak or cable problem is
no longer present.
Select Yes (latching) or No (non-latching).
Default setting: No (non-latching alarms)
Audible Alarm
Select Enabled to activate the audible alarm annunciation. Disable
this option to deactivate the audible alarm annunciation.
Default setting: Disabled
Length Calibration
Factor
Reserved for manufacturer’s use only.
Option
Description
Table 3.2
Leak Configuration Options