beautypg.com

Zone settings, Figure 3.5 zone configuration, Table 3.3 – RLE LD2100 V.2.6 User Manual

Page 33: Zone settings configuration options, 2 zone settings

background image

rletech.com

LD2100 User Guide

33

3

Web Interface

3.3.2 Zone Settings

You can set up the LD2100 to identify different areas where leak detection cable or spot

detectors are installed. Each area is called a zone. Up to 32 zones can be configured on the

LD2100 - the LD2100 itself is the master controller, and up to 31 slave units can connect to it.

Dividing a leak detection system into zones helps locate leaks quickly. It can also simplify

troubleshooting by allowing you to isolate different sections of cable and different rooms or

other defined areas. The LD2100 uses two different types of zones:

Physical zone. A physical zone consists of a single SeaHawk distance read controller,

including the LD2100 and other RLE distance read controllers attached to it, and the

attached sensing cable. In a scenario where additional controllers are attached, the LD2100

acts as a Modbus master to other controllers. To configure physical zones, including setting

up the LD2100 as a Modbus master attaching additional controllers, follow the instructions

in

Chapter 4

.

Virtual zone. A virtual zone is a labeled reference point in a leak detection system. A

virtual zone can consist of a room, a drip pan containing a spot detector under an air handler

unit, a combination of rooms and components, or any other defined area whose

identification would help in the location of leaks.

If you wish to establish virtual zones, go to Configuration>Zone Settings. The Zone

Configuration page displays. Select the desired zone settings.

Figure 3.5

Zone Configuration

Option

Description

Zones 0 - 32

Enter an integer from 0 to 32 to indicate the number of virtual zones

you want to configure.

Modbus Zone Traps

Select the Enable radio button to enable SNMP traps for the Leak

Detection Modbus master. Default: Disable.

Enable Alarm Relay

for Modbus Slaves

Select the Enable radio button to activate the summary alarm when a

leak detection slave unit goes into an alarm. Default: Disable

Table 3.3

Zone Settings Configuration Options