3.3.14 Alarm Management
Use this page to manage and reset current alarms, messages, and alarm history.
Figure 3.23
Alarm Management Page
Number_of_APDU_
Retries
The maximum number of times and APDU is retransmitted.
Send Test Alarms
Click this button to test your alarm configuration. Press the submit
changes button before clicking this link, or all your BACnet
configuration data will be lost.
Clear Test Alarms
Click this button to clear the test alarms once they have been sent
and correctly received.
Option
Description
Reset Leak Alarm
Resets the current leak alarm and causes the LD2100 to recheck the
current cable conditions. This clears the alarm condition if the cable
registers that the leak threshold is within an accepted range.
Clear Alarm History
View the alarm history through the Historical Data link at the top of
the web interface. Click this button to clear the alarm history of all
previous alarms.
Acknowledge
Unsent Emails
Clears unsent emails so they aren’t sent to recipients. Events are still
logged in the historical data.
Acknowledge Snmp
Informs
Acknowledges SNMP Informs and stops Informs from being sent out
for the current alarm condition.
Enable Power Up
Alarm Logging
Check this box and click the Submit button to log an alarm when the
LD2100 powers up. This way, if the power cycles on the unit, you will
be able to look in the alarm history log and see a record of the
activity.
Table 3.14
Alarm Management Options