RLE LD2100 V.2.6 User Manual
Page 31

rletech.com
LD2100 User Guide
31
3
Web Interface
Leak Alarm Delay
The amount of time that passes between the time a leak is detected
and the annunciation of the leak alarm.
The leak trip point must be exceeded for the duration of this delay.
Default setting: 20 seconds
Contamination
Alarm Delay
The amount of time that passes between the time a contamination
is detected and the annunciation of the contamination alarm.
The contamination trip point must be exceeded for the duration of
this delay.
Default setting: 40 seconds
Resistance Per Foot
The resistance per foot (or meter) of cable determines the
LD2100’s ability to accurately detect the cable length installed and
calculate distances to leaks. Adjust this value to fine-tune the
accuracy of a distance-read leak detection system.
RLE’s orange water sensing cable has a base resistance of 2.800
ohms per foot. Most other sensing cables, including RLE’s green
chemical-resistant sensing cable, have a base resistance of 4.000
ohms per foot. Consult the sensing cable’s datasheet for further
information.
The resistance value must be entered as a 4-digit number between
2.000 and 4.250, with one number in the tens place and three
numbers past the decimal point (x.xxx).
Default setting: 2.800 ohms per foot
Re-Alarm Interval
The LD2100 can be set to re-alarm - after a leak or contamination
has been detected, the alarm will be re-sent at a defined interval
until the alarm condition has been resolved. The re-alarm triggers
both the audible alarm and the direct notification alarm.
Enter a number from 0 to 24. A 0 in this field turns off the re-alarm
option, so only one alarm notification will be sent for each alarm.
Default setting: 0 (disabled)
Measurement
Display
Select either feet or meters to calibrate the LD2100 to the preferred
unit of measure. All distance calculations will adjust accordingly.
Default setting: Feet
Option
Description
Table 3.2
Leak Configuration Options