Configure communications through the eia-232 port – RLE LD2100 V.2.6 User Manual
Page 22

22
LD2100 User Guide
800.518.1519
2
Installation
If the login window for the LD2100 does not display:
a
Verify that all cables are firmly attached.
b
Verify that you entered the correct IP address for the LD2100.
c
Verify that the Status light on the top of the LD2100 is green.
For further troubleshooting information, refer to
2.8.
Configure Communications Through the
EIA-232 Port
You can also use the EIA-232 interface to set the IP address:
1
Connect the EIA-232 port (P4) on the LD2100 to a terminal or PC running terminal
emulation software (HyperTerminal) with a 9-pin male-female straight through serial cable.
2
2. Set the appropriate communication port to 9600 baud, NO parity, 8 data bits, 1 stop
bit, (9600/N/8/1), and no software or hardware flow command.
3
Once the terminal emulation software starts, type
?
and press Enter on the keyboard and the
Main Menu should appear. If the Main Menu does not appear, check the communication
settings and make sure the unit is powered on.
4
From the Main Menu type netcfg to select the Network Configuration Menu.
♦
Enter the new IP address for the LD2100 by typing
ip xxx.xxx.xxx.xxx
, where
xxx.xxx.xxx.xxx
is the new IP address of the unit. Separate each field with a decimal
point. For example, type
ip 10.0.0.50
.
♦
The LD2100 erases a memory block and copies data to flash memory before rebooting.
♦
The LD2100 IP address is now set and the LD2100 can be accessed through a Web
browser using the new IP address.
5
to change the Subnet Mask and Def Route, if needed, using the commands
nm
xxx.xxx.xxx.xxx
to change the Subnet Mask and
dg xxx.xxx.xxx.xxx
to change the default
gateway.