Table 5.6, Status flags (register 30001) – RLE LD2100 V.2.6 User Manual
Page 73

rletech.com
LD2100 User Guide
73
5
Modbus Communication
30066
Modbus Zone28
Distance
Location of leak
Ft/Meters
0-65535
30067
Modbus Zone29 Status
Bit Level Status
None
0-65535
30068
Modbus Zone29
Distance
Location of leak
Ft/Meters
0-65535
30069
Modbus Zone30 Status
Bit Level Status
None
0-65535
30070
Modbus Zone30
Distance
Location of leak
Ft/Meters
0-65535
30071
Modbus Zone31 Status
Bit Level Status
None
0-65535
30072
Modbus Zone31
Distance
Location of leak
Ft/Meters
0-65535
30073
Modbus Zone32 Status
Bit Level Status
None
0-65535
30074
Modbus Zone32
Distance
Location of leak
Ft/Meters
0-65535
30075
Virtual Zone Alarm
Status
Bit Level Status
None
0-65535
Table 5.5 Input Registers (continued)
Register
Name
Description
Units
Range
Table 5.6 Status Flags (Register 30001)
Bit
Description
00
1 = Leak is Detected
01
1 = Cable Break Alarm
02
1 = Contamination is detected
04-15
Spare