RLE LD2100 V.2.6 User Manual
Page 24
24
LD2100 User Guide
800.518.1519
2
Installation
For example:
One 15 foot leader cable (leader cable does not count toward the total length of cable
installed), one weighted cable connector (simulates 50 feet of cable), and one 330 foot
section of cable are connected to the system.
The actual resistance of the cable installed with this LD2100 is 2.881 ohms per foot.
6
Go to the Leak Configuration page (Configuration>Leak Settings) and enter the newly
calculated Resistance Per Foot value. Click Submit Changes once you have made all your
changes to this web page.
When using the web interface, remember to click the Submit Changes button to save the
adjusted resistance value.
In our example, adjusting the resistance value changed the reported cable length from 391
feet to 380 feet. This improves the accuracy of the system because the reported cable length
more closely matches the physical length of cable connected to the system.
Cable Length (as reported by the LD2100)
391 feet
Cable Current
0
μA
Leg 1 Resistance
1088 Ohms
Leg 2 Resistance
1095 Ohms
Reported Resistance
2.800 Ohms/foot
Actual length of cable connected to LD2100
0 feet + 50 feet + 330 feet
380 feet