Configure modbus communications – RLE LD2100 V.2.6 User Manual

Page 63

background image

rletech.com

LD2100 User Guide

63

4.3. Configure

Modbus

Communications

Log into the LD2100 web interface and configure the unit to be a Modbus master:

1

From the Home page, click the Configuration link in the top bar. If using the EIA-485 port,

click on EIA-485 Port/Modbus/N2.

2

Once on the Modbus/EIA-485 Configuration page, select Modbus-Master or N2 from the

Select EIA-485 Port Function drop down. When completed, click on the submit changes

tab.

Figure 4.3

Modbus/EIA-485 Configuration, Modbus Master

Next, configure the slave units:

3

From the LD2100 Home page, click the Configuration link in the top bar. Choose from the

following options based on the configuration you want to set up:

a

Use any of the zone addresses, 1 through 32, that are still available after virtual zones

have been configured.

b

If you are not using the virtual zone feature, check the Physical-Modbus/485 option.

Trap notifications can be enabled or disabled on individual units via the Modbus/EIA-

485 Configuration webpage. Click the submit changes button to save changes. Return to

the Configuration webpage when finished.

Figure 4.4

Zone Configuration Webpage