Product Overview

1.2. Operation

Supervised System

The LD2100 is a supervised system — it continually monitors the leak detection cable and spot

detectors for continuity. In addition to a leak triggering an alarm condition, a cable break or

excess contamination of the cable causes a cable fault indication and activates a relay. The

LD2100 sends alarm notifications to predetermined recipients when an alarm sounds. The

LD2100 produces an alarm during the following conditions:

Leak detection

Cable break

Cable contamination

Distance-Read Leak Detection

When the LD2100's circuitry measures a current in excess of the user-defined leak threshold,

the unit's microprocessor computes the distance to the leak. The LD2100 then annunciates the

leak and logs the alarm in its event log. The summary relay has one output.

User Communication

A Web-based user interface provides information about the LD2100’s conditions. The user

interface can be used on site or remotely via network communications. The chapters and

appendices in this manual describe how to use the interface to accomplish specific

configuration and operation tasks.

The LD2100 also provides Modbus outputs via EIA-485, twisted-pair wire, or TCP/IP, as well

as BACnet/IP or BACnet/MSTP and SNMP outputs.