Installation

2.9.

Calibrate Cable Resistance

Distance-read leak detection systems are resistance-based. RLE’s orange water sensing cable

has a base resistance of 2.8 ohms/foot, while most other sensing cables, including RLE’s green

chemical resistant sensing cable, have a resistance of 4.0 ohms/foot.

The resistance of each length of sensing cable may be slightly more or less than the base

resistance due to manufacturing variances. For this reason, the cable length displayed on the

home page of the web interface may be slightly more or less than the actual length of cable

installed.

A system configured using base resistance values will still be very accurate. If you wish to fine

tune the resistance value of your LD2100 system to make it more precise, you may do so. This

will increase the accuracy of the system, and bring the LD2100’s reported installed cable

length value in line with the actual length of cable installed.

1

Ensure the LD2100 has been powered and has all the sensing cable attached to it, with no

alarms present.

2

Gather and record the following data from the home page of the web interface:

Record the resistance per foot setting, as reported by the LD2100. This can be found on the

Leak Configuration page of the web interface (Configuration > Leak Settings).

3

Note the actual (physical + simulated) length of cable physically connected to the system.

For your reference:

Record this sum:

4

Verify the current reading on the cable from the recorded value above. This value must be

less than 15

μA in order to calibrate the system. If the current is higher than 15μA, clean the

cable. Isopropyl alcohol works well to remove any contamination that might have gotten

onto the cable during installation.

5

To calculate the most accurate resistance value for the system, divide the reported cable

length by the actual cable length, and multiply the quotient by the reported resistance.

Cable Length (as reported by the LD2100)
Cable Current
Leg 1 Resistance
Leg 2 Resistance

Reported Resistance per Foot

WCCS simulates 50 ft.

XCON simulates 150 ft.

SDZ simulates 50 ft.

Nonsensing cable does not add

any length to a system

Actual length of cable connected to LD2100