LD2100 User Guide

800.518.1519

4.2. Connect

Distance-Read Panels Through the

Ethernet Port

When using the LD2100 as a Modbus master, the slave unit(s) can be connected to the

LD2100 by using the local network connection, either TCP/IP or UDP/IP, as follows:

Set the TCP/IP, UDP/IP slave address for each leak detection unit with distance-read

controllers that have an Ethernet port as follows:

1

Connect the slave units to the network using the Ethernet ports on the units.

2

Set the TCP/IP, UDP/IP slave address for each distance-read module connected over the

Ethernet by following these guidelines:

Modbus communication uses port #502 for the IP address assigned.

Set the first unit connected to address 2 or higher.

Increase the address for each subsequent unit in numeric order by one (for example, the

next unit would be set to address 3).

Figure 4.2

Ethernet Connection Diagram