3.3.1 Leak Settings
Use the Leak Configuration page to fine tune system variables, including leak and
contamination thresholds, latching and unlatching alarms, and sensing cable resistance.
Figure 3.4
Leak Settings Configuration
Option
Description
Leak Trip Point
The threshold for the amount of water required to trigger a leak
alarm. Adjust this number to adjust the sensitivity of the leak alarm.
A lower number yields a more sensitive system, so the system will
trigger a leak alarm with less water present.
A higher number produces a less sensitive system, so more water
is required to trigger an alarm.
Enter a value between 25 and 295 microamps.
Default setting: 150uA
Contamination Trip
Point
The threshold for the amount of contamination required to trigger a
cable contamination alarm. Adjust this number to adjust the
sensitivity of the contamination alarm.
A lower number yields a more sensitive system, so the system will
trigger a contamination alarm with less contamination present.
A higher number produces a less sensitive system, so more
contamination is required to trigger an alarm.
Enter a value between 20 and 295 microamps.
Default setting: 50uA
Table 3.2
Leak Configuration Options