Power SuPPly SetuP
2-10
powermax
105
Service Manual
Engine-driven generator recommendations
Generators used with the Powermax105 should satisfy the following requirements:
200–600 V CSA
3-phase, 50/60 Hz, 200–600 VAC (480 VAC recommended for best performance)
230–400 V CE
3-phase, 50/60 Hz, 230–400 VAC (400 VAC recommended for best performance)
380 V CCC/230–400 V CE
3-phase, 50/60 Hz, 230–400 VAC (400 VAC recommended for best performance)
400 V CE
3-phase, 50/60 Hz, 400 VAC (400 VAC recommended for best performance)
380 V CCC
3-phase, 50/60 Hz, 380 VAC (380 VAC recommended for best performance)
Engine drive
rating
System output
current
Performance
(arc stretch)
30 kw
105 A
Full
22.5–25
105 A
Limited
20 kw
85 A
Full
15 kw
70 A
Limited
15 kw
65 A
Full
12 kw
65 A
Limited
12 kw
40 A
Full
8 kw
40 A
Limited
8 kw
30 A
Full
Note: Based on the generator rating, age, and condition, adjust the cutting current as needed.
If a fault occurs while using a generator, turning the power switch quickly to OFF and then to ON again
(sometimes called a “quick reset”) may not clear the fault. Instead, turn OFF the power supply and wait 60 to
70 seconds before turning ON again.