PFC-4410RC • 5403550 • REV Q • 11/12

CAM

CLASS A INDICATING

APPLIANCE CIRCUIT MODULE

The Model CAM Class A Module is designed to be used with the

PFC-4410RC Fire Control Releasing Panel to convert a single (Class

B) indicating appliance circuit to a (Class A) circuit (one module is

required for each indicating appliance circuit). After installing the

Stock number: 3005300

UL LISTED: OPTION FOR USE WITH THE PFC-4410RC SERIES

TRANSIENT PROTECTED

POWER REQUIREMENTS IN ALARM:

APPROXIMATELY 25 MA AT 24VDC FROM CONTROL PANEL

INDICATING APPLIANCE CIRCUIT.

BUILT IN, POLARIZED, 5.1K END OF LINE RESISTOR

TERMINAL BAR

CAM

MODULE NO.

1

CAM

MODULE NO.

2 (IF USED)

5 1/2”

1/2”

1/2”

BATTERY

BATTERY

CAM

EXTERNAL

INDICATING

APPLIANCES

DWG# 927-15

TO INDICATING

APPLIANCE CIRCUIT

TERMINALS. POLARITY

SHOWN IS FOR ALARM

CONDITION. REMOVE

EOL RESISTOR

BLACK

RED

1 2 3 4

MFG. #5400927 - REV L

9/08

PRINTED IN USA

PAGE 1 OF 1

Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-572-3005 • Tech Support: 866-956-0988 • Canada 888-882-1833

• www.pottersignal.com

CAM, the indicating circuit should be activated to ensure proper

operation and connections.

The module is provided with double sided foam tape and should

be mounted in the area below the main circuit module so that the

terminals are accessible.

Mounting

Typical Wiring