Class a indicating appliance circuit module – Potter PFC-4410RC User Manual
Page 99
99
PFC-4410RC • 5403550 • REV Q • 11/12
CAM
CLASS A INDICATING
APPLIANCE CIRCUIT MODULE
The Model CAM Class A Module is designed to be used with the
PFC-4410RC Fire Control Releasing Panel to convert a single (Class
B) indicating appliance circuit to a (Class A) circuit (one module is
required for each indicating appliance circuit). After installing the
Stock number: 3005300
UL LISTED: OPTION FOR USE WITH THE PFC-4410RC SERIES
TRANSIENT PROTECTED
POWER REQUIREMENTS IN ALARM:
APPROXIMATELY 25 MA AT 24VDC FROM CONTROL PANEL
INDICATING APPLIANCE CIRCUIT.
BUILT IN, POLARIZED, 5.1K END OF LINE RESISTOR
TERMINAL BAR
CAM
MODULE NO.
1
CAM
MODULE NO.
2 (IF USED)
5 1/2”
1/2”
1/2”
BATTERY
BATTERY
CAM
EXTERNAL
INDICATING
APPLIANCES
DWG# 927-15
TO INDICATING
APPLIANCE CIRCUIT
TERMINALS. POLARITY
SHOWN IS FOR ALARM
CONDITION. REMOVE
EOL RESISTOR
BLACK
RED
1 2 3 4
MFG. #5400927 - REV L
9/08
PRINTED IN USA
PAGE 1 OF 1
Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-572-3005 • Tech Support: 866-956-0988 • Canada 888-882-1833
• www.pottersignal.com
CAM, the indicating circuit should be activated to ensure proper
operation and connections.
The module is provided with double sided foam tape and should
be mounted in the area below the main circuit module so that the
terminals are accessible.
Mounting
Typical Wiring