Potter PFC-4410RC User Manual
Page 69

69
PFC-4410RC • 5403550 • REV Q • 11/12
Program #27 Mode
1. Apply power to panel.
2. Move the program switch down.
3. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”
4. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET
button to move to the next digit. After entering the third number the display will change.
(All panels are shipped with a 000 password.)
5. Press the FUNCTION (bottom) button until the display reads “PROGRAM #0”.
6. Press the SELECT button until the display reads “PROGRAM #27”.
7. Press the SET button.
8. Press the SELECT button to change the pre-discharge time.
9. Press the SET button to enter the pre-discharge time displayed.
10. Press the SELECT button to change the abort mode. See page 11 for abort selections.
11. Press the SET button to enter the abort mode displayed.
12. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.
Description:
Single Hazard, 2 detection zones cross-zoned to 1 eAEROSOL
Inputs:
1 supervisory zone, 3 detection zones, 1 abort circuit, a manual station zone
Outputs:
3 general alarm, 1 eAEROSOL circuit
Operation:
Activation of either detection zones 1 or 2 will activate the alarm output #1
Activation of both detection circuits at the same time will activate the alarm outputs #1, #2 and start the pre-
discharge timer for the eAEROSOL circuit output #3
Activation of the manual release zone 3 will activate the alarm output #2 and start the manual release pre-
discharge timer for the eAEROSOL circuit output #3
Activation of zone 4 will operate output #4
When either zone 1 or 2 is in alarm, output 1 will operate
When both zones 1 and 2 are in alarm at the same time, outputs #1,2 will operate and the pre-discharge timer for
output #3 will start
When zone 3 is in alarm, output #2 will operate and the manual release pre-discharge timer for output #3 will start.
When zone 4 is in activated, output #4 will operate.
PROGRAM #27
ZONES
SUPERVISORY 2
#1
#2
#3
#4
OUTPUTS
Supervisory
Detection
Detection
Manual Release
Detection
#1 FIRST ALARM
X
X
#2 SECOND ALARM
X
X
X
#3 eAEROSOL
XX
XX
X
#4 ALARM INDICATING
X
SUP 1 defaults to abort
XX = Cross-Zoned