beautypg.com

Potter PFC-4410RC User Manual

Page 45

background image

45

PFC-4410RC • 5403550 • REV Q • 11/12

Program #12 Mode

1. Apply power to panel.
2. Move the program switch down.
3. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.
4. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET

button to move to the next digit. After entering the third number the display will change.
(All panels are shipped with a 000 password.)
5. Press the FUNCTION (bottom) button until the display reads “PROGRAM #0”.
6. Press the SELECT button until the display reads “PROGRAM #12”.
7. Press the SET button.
8. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.

Description:

Single Hazard, 2 detection zones,1 waterflow, and 3 supervisory zones.

Inputs:

1 supervisory zone, 1 low air supervisory zone, 2 detection zone, 1 waterflow zone, 1 tamper switch zone.

Outputs:

2 general alarm, 1 waterflow, 1 solenoid release circuit

Operation:

Activation of either detection zone will operate the release and the general alarm bell outputs.

Activation of the waterflow zone will operate the waterflow and both general alarm bell outputs. Activation of

either the tamper or supervisory zones will operate the supervisory relay only.

When either zone 1 or 2 is in alarm, outputs 1 & 3 will operate

When zone 3 or the supervisory zone is activated, only the supervisory relay operates

When zone 4 is in alarm, outputs 1, 2 & 4 will operate

PROGRAM #12

ZONES

SUP 1

SUP 2

#1

#2

#3

#4

OUTPUTS

Supervisory

Low Air

Supervisory

Detection

Detection

Tamper

Waterflow

#1 ALARM INDICATING

X

X

X

#2 ALARM INDICATING

X

#3 RELEASE

X

X

#4 ALARM INDICATING

X