After describing all initiating zones or skipping to the next function, the following will appear in the display window:
Supervisory 1 is a supervisory or abort zone and can only be described as SUPERVISORY, TAMPER, LOW AIR or HIGH AIR, or ABORT.
SET
Press the SET button to set the description displayed.
SELECT
Press the SELECT button to scroll through the four supervisory and abort descriptions.
FUNCTION
Press the bottom button to skip to the next function.
After describing what the supervisory zone is to be or skipping to the next function, the following will appear in the display window:
SET
Press the SET button to set the description displayed.
SELECT
Press the SELECT button to scroll through the four supervisory and abort descriptions.
FUNCTION
Press the bottom button to skip to the next function.
After describing what the supervisory zone is to be or skipping to the next function, the following will appear in the display window:
Output Description
This allows the user to describe the functions of the output circuits. Four descriptions are available:
1) ALARM INDICATING - Indicating appliances include bells, horns, strobes and other appliances used to indicate an alarm.
2) RELEASING - Releasing appliances include solenoids and other electrically compatible devices.
3) eAEROSOL – To be used with Aerosol Generators only. Pulse Releasing Output, 1/16th sec on, 15/16th sec off. Available only
with chemical programs. Will turn off after 200 pulses (200 seconds).
4) SUPERVISORY BELL - Appliances on this circuit are used to indicate the presence of a supervisory condition. Any zone
programmed as LOW AIR ALARM, SUPERVISORY, TAMPER, HI AIR or LOW AIR is automatically mapped to this output.
5) TROUBLE BELL - Appliances on this circuit are used to indicate the presence of a trouble condition. The user should describe
each output circuit in the same manner as the initiating circuit was described by pressing the middle button to select and the
top button to set the desired function.
SET
Press the top button to set the description displayed.
SELECT
Press the middle button to scroll through the descriptions.
FUNCTION
Press the bottom button to skip to the next function.
After selecting all four outputs or pressing FUNCTION, the following will be displayed if any outputs have been
described as RELEASING:
O U T P U T
# 1
I N D I C A T I N G
O U T P U T
# < a >
N O R M A L
S U P E R V S R Y
1
Z O N E
S U P E R V I S R Y
S U P E R V S R Y
2
Z O N E
S U P E R V I S R Y