beautypg.com

Potter PFC-4410RC User Manual

Page 52

background image

52

PFC-4410RC • 5403550 • REV Q • 11/12

The following programs are for chemical or gas extinguishing systems. Selecting the CHEMICAL mode allows the use of a pre-

discharge timer and an abort circuit. The timer defaults to 60 seconds for all alarm zones programmed as other than MANUAL

RELEASE. The MANUAL RELEASE default timer is 30 seconds. The system offers the programmer the ability to change the

default timers to shorter times.

Systems intended for the release of Halon 1301 as described in NFPA 12A, or clean agents as described in NFPA 2001, shall

have provision for a pre-discharge notification circuit. If this signal is required to be separate and/or distinct from the evacuation

signal, two notification circuits are required. One shall be programmed as FIRST ALARM. It will provide a steady output upon

activation of any initiating zone programmed as an alarm zone. This is the evacuation signal. If a temporal signal is required,

notification appliances such as Amseco model HW-24R or others that can produce a temporal tone shall be used. This allows the

use of strobes and horns on the same circuit. The other notification circuit shall be programmed as SECOND ALARM. It will

provide a steady output upon activation of a second initiating zone programmed as an alarm zone. This is when the pre-discharge

timer would start and would be the pre-discharge signal. If a temporal signal is required, notification appliances such as Amseco

model HW-24R or others that can produce a temporal tone shall be used. This allows the use of strobes and horns on the same

circuit. If a separate signal for discharge were required, a third notification circuit would be used that would be programmed to

operate whenever the release circuit is activated.

Zones programmed as MANUAL RELEASE will activate outputs programmed as SECOND ALARM, even if the MANUAL

RELEASE zone is the first alarm zone activated. SECOND ALARM is intended to be used as a pre-discharge signal for cross

zone applications. Refer to page 50 for a complete description of first and second alarm requirements and operation.

NOTE:

On programs 20-28, the SUP 1/Abort zone defaults to Abort.

Z

ones

programmed

as

m

anual

r

elease

Cannot

be

aborted

. i

f

it

is

neCessary

to

abort

a

manual

release

Zone

,

that

Zone

must

be

programmed

as

d

eteCtion

. i

f

the

pre

-

disCharge

timer

is

set

at

0,

the

abort

CirCuit

Will

not

stop

the

release

.

NFPA 12 prohibits the use of abort circuits on suppression systems deploying carbon dioxide.

Systems designed and installed in accordane with NFPA 2001 shall be provided with a mechanical manual release system.