PFC-4410RC • 5403550 • REV Q • 11/12

Program #23 Mode

1. Apply power to panel.
2. Move the program switch down.
3. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”
4. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET

button to move to the next digit. After entering the third number the display will change.
(All panels are shipped with a 000 password.)
5. Press the FUNCTION (bottom) button until the display reads “PROGRAM #0”.
6. Press the SELECT button until the display reads “PROGRAM #23”.
7. Press the SET button.
8. Press the SELECT button to change the pre-discharge time.
9. Press the SET button to enter the pre-discharge time displayed.
10. Press the SELECT button to change the abort mode. See page 10 for abort selections.
11. Press the SET button to enter the abort mode displayed.
12. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.

Description:

Single Hazard, 4 detection zones mapped to 1 release

Inputs:

1 supervisory zone, 4 detection zones, 1 abort circuit

Outputs:

1 general alarm, 1 trouble, 1 supervisory, 1 release circuit

Operation:

Activation of any detection zone will activate the alarm output #1 and start the pre-discharge timer for the

release circuit output #4.

Activation of the supervisory zone will operate the supervisory bell.

A trouble condition (low battery, wire problem, etc.) will operate the trouble bell.

When either zone 1, 2, 3, or 4 is in alarm, outputs 1 & 4 will operate

When the supervisory zone is activated - output #3 (supervisory bell) will operate.

When the panel is in a trouble condition - output #2 (trouble bell) will operate.

PROGRAM #23

ZONES

SUPERVISORY 2

#1

#2

#3

#4

OUTPUTS

Supervisory

Detection

Detection

Detection

Detection

#1 ALARM INDICATING

X

X

X

X

#2 TROUBLE
#3 SUPERVISORY

X

#4 RELEASE

X

X

X

X

SUP 1 defaults to abort