Potter PFC-4410RC User Manual
Page 84
![background image](/manuals/708724/84/background.png)
84
PFC-4410RC • 5403550 • REV Q • 11/12
Mounting Instructions
1) The unit should be mounted in a convenient location, approximately 5 ft. from the floor where it will be
accessible for testing and servicing.
2) The main circuit board module should be removed before attempting to mount the cabinet. Disconnect the AC power from
TB201. To remove the module, remove the two screws holding the chassis to the cabinet. Lift the module upwards, approximately
1/2", in order to clear the cross-beam of the cabinet on which the module rests. Remove the module and set aside.
3) The PFC unit may be surface mounted or semi-flush mounted using the optional trim bezel. (See drawing for installation
of bezel on page 84). For semi-flush installations mount the housing so that the front edge protrudes 1" from the finished wall
surface. After all conduits and wiring are in place and the wall surface is completely finished, slide the trim bezel in place and
fasten with 4 #6-32 x 1/4" machine screws and nuts.
4) Install all required conduits, external wiring and devices and make all connections that are external to the panel. Replace
the module. With the AC power still turned off at the circuit breaker panel, connect the AC hot, neutral and ground wires to the
terminal block TB201 as shown on the connection drawing. (See connection drawings on page 88)
5) Connect all the other wiring to the terminals as shown in the connection drawings. Turn the AC power on and connect the
standby batteries with the cable provided, polarity must be observed.
6) Replace false front panel and secure with mounting screws, taking care to not damage LED annunciator module cable.
7) The operation of the complete system should be verified as outlined in the test procedure section.
PFC-4410RC False Front Removal/Assembly Drawing
Removal of this false front exposes electrical
components at potentially hazardous voltages and
should be performed by qualified personnel only.
DWG# 3550-15