PANEL INPUTS (INITIATING ZONES)

CONNECT TO NORMALLY OPEN DEVICES

OR COMPATIBLE 2 WIRE SMOKE

DETECTORS.

MAXIMUM LINE RESISTANCE: 100 OHMS

(EXCEPT WITH LINEAR HEAT DETECTION)

OPTIONAL CA2Z MOUNTING LOCATION

5.1K

VALVE

TAMPER

OSYSU

PCVS

5.1K

EOLR

5.1K

EOLR

5.1K

EOLR

5.1K

EOLR

5.1K

EOLR

AUX.

POWER

24VR DC

SUP 1/

ABORT

SUPV 2

ZONE 1

HEAT OR

SMOKE

DETECTORS

ZONE 2

LOW AIR

ALARM

ZONE

ZONE 3

HEAT OR

SMOKE

DETECTORS

ZONE 4

LOW AIR

ALARM

ZONE

EACH CA2Z WILL

CONVERT 2 CLASS B

ZONES INTO 2 CLASS A

ZONES

OPTIONAL CLASS A

CONNECTIONS EOLR IS

NOT USED FOR CLASS A

OPTIONAL

CA2Z CLASS

A MODULE

DWG #3550-20

NO

COM

NC

NC

NO

NO

NO

COM

COM

COM

TROUBLE

SUPV

ALARM

SUPERVISORY

LOW AIR

VALVE TAMPER

WTRFL

ALARM CONDITION

SMOKE DET.

HEAT DET.

PULL STATION

WATERFLOW

WATERFLOW

TROUBLE CONDITION

PANEL PROBLEM

LOSS OF AC

LOSS OF BATTERY

WIRING PROBLEM

RELAY CONTACTS

DRY CONTACTS RATED AT 3A, 30VDC RESISTIVE

EOL

DIODE

ASSY

5.1K

EOLR

EOL

DIODE

ASSY

5.1K

EOLR

RE

D

RE

D

RE

D

RE

D

RE

D

BLAC

K

BLAC

K

BLAC

K

BLAC

K

BLAC

K

12V BATT.

12V BATT.

POS

NEG

POS

NEG

BATTERY CABLE

OBSERVE POLARITY

RED +

BLACK -

PANEL OUTPUTS (INDICATING CIRCUITS)

RELEASE

CIRCUIT

OUTPUT

4

GENERAL

ALARM

BELL

OUTPUT

3

RELEASE

CIRCUIT

OUTPUT

2

GENERAL

ALARM

BELL

OUTPUT

1

NON-POWER

LIMITED AND

SUPERVISED

BATT

PROGRAM

SWITCH

NON-POWER

LIMITED AND

SUPERVISED

AC IN

CONNECTOR

EARTH GROUND - GREEN

NEUTRAL - WHITE

HOT - BLACK

TO CIRCUIT BREAKER PANEL

120VAC/60Hz

165 VA MAX.

1120VAC/50Hz

185 VA MAX.

24VNR DC RS-485

S

120 OHM

OBSERVE POLARITY

WHEN CONNECTING

SMOKE DETECTORS

ZONE 1

ZONE 2

ZONE 3

ZONE 4

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

PROGRAM

MODE

RUN

MODE

AC POWER

POWER TBL

SYSTEM TBL

SUP TBL
GROUND

FAULT

SUP 1/ABORT

SUPERVISORY 2

COMMON ALARM

ALARM SILENCE
STEADY: DISCHARGING

FLASHING: PRE-

DISCHARGE

RUN

PROGRAM

SET

SELECT

FUNCTION

SCROLL-DOWN

BUZZER SILENCE

SIGNAL SILENCE

SYSTEM RESET

SCROLL-UP

BUZZER SILENCE

VIEWING ANGLE

RED OUTPUT LED STEADY: ABORT

N

120

See page 89 or label inside panel door for smoke detector

compatibility data.

See page 85 for battery information.

Wiring Diagram Program #15

Dual Hazard, 1 Detection Zone and 1 Low Air Alarm Zone Cross-Zoned to 1 Release Circuit, 1 Other

Detection and 1 other Low Air Alarm Zone Zone Cross-Zoned to a Separate Release Circuit, and

Supervisory Zones.

}

LAMP TEST

10. Maximum resistance on outputs is 10 ohms. Maximum

resistance on outputs programmed as releasing, is 1

divided by current requirements of solenoid.

11. Notification outputs do not provide synchronization.

If synchronization is needed, refer to the NAC table on

page 90. Synchronization is only on one circuit and not

betweeen circuits. The maximum cannot exceed 1 amp or

whatever the maximum that the sync' module can support,

whichever is lower.

NOTES:

1. Connect only UL Listed 24VDC devices to indicating

circuits.

2. Connect EOL Diode assembly IN SERIES with solenoid

on release circuit

3. Leave EOLR (provided) on all unused circuits.

4 Polarity is shown on indicating circuits in an activated

(off-normal) condition.

5. Polarity reverses when output is activated.

6. Maximum current per output is 1 Amp. Maximum voltage

is 33VDC.

7. Outputs identified as Release are Special Application. All

other outputs are Regulated 24 VDC, Rated 1 Amp each,

2.5 Amp total for all 4 circuits.

8. All initiating and NAC/Release circuits are supervised and

power limited. See note 3 on page 92 for power limited

wire routing instructions. All frequencies are continuous.

9. Refer to pgs. 16, 83-85 for installation, test and

maintenance information.

S

Initiating device

Notification appliance

Solenoid

End-of-Line diode assy

Legend