Program #15 Mode

1. Apply power to panel.
2. Move the program switch down.
3. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.
4. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET

button to move to the next digit. After entering the third number the display will change.
(All panels are shipped with a 000 password.)
5. Press the FUNCTION (bottom) button until the display reads “PROGRAM #0”.
6. Press the SELECT button until the display reads “PROGRAM #15”.
7. Press the SET button.
8. The panel is completely programmed except for the custom banner and zone messages Move the program switch back up.

Description:

Dual Hazard, 2 detection zones cross-zoned* to 1 release circuit and 2 other detection zones cross zoned to

another release circuit

Inputs:

2 supervisory zones, 4 detection zones

Outputs:

2 general alarm, 2 release circuit

Operation:

Activation of either detection zones 1 and 2 will activate the alarm output #1

Activation of both detection circuits at the same time will release circuit output #2 as well as activate the alarm

output #1

Activation of either detection zones 3 and 4 will activate the alarm output #3

Activation of both detection circuits at the same time will release circuit output #4 as well as activate the alarm

output #3

When either zone 1 or 2 is in alarm, output 1 will operate

When both zones 1 and 2 are in alarm at the same time, output #2 will operate

When either zone 3 or 4 is in alarm, output 3 will operate

When both zones 3 and 4 are in alarm at the same time, output #4 will operate

*Cross Zoning acceptable for NFPA 13, 15, and 16 type extinguishing systems.

PROGRAM #15

ZONES

SUP 1

SUP 2

#1

#2

#3

#4

OUTPUTS

Supervisory

Detection

Low Air Alarm

Detection

Low Air Alarm

#1 ALARM INDICATING

X

X

#2 RELEASE

XX

XX

#3 ALARM INDICATING

X

X

#4 RELEASE

XX

XX

XX = Cross-Zoned