Potter PFC-4410RC User Manual
Page 51
51
PFC-4410RC • 5403550 • REV Q • 11/12
Program #15 Mode
1. Apply power to panel.
2. Move the program switch down.
3. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.
4. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET
button to move to the next digit. After entering the third number the display will change.
(All panels are shipped with a 000 password.)
5. Press the FUNCTION (bottom) button until the display reads “PROGRAM #0”.
6. Press the SELECT button until the display reads “PROGRAM #15”.
7. Press the SET button.
8. The panel is completely programmed except for the custom banner and zone messages Move the program switch back up.
Description:
Dual Hazard, 2 detection zones cross-zoned* to 1 release circuit and 2 other detection zones cross zoned to
another release circuit
Inputs:
2 supervisory zones, 4 detection zones
Outputs:
2 general alarm, 2 release circuit
Operation:
Activation of either detection zones 1 and 2 will activate the alarm output #1
Activation of both detection circuits at the same time will release circuit output #2 as well as activate the alarm
output #1
Activation of either detection zones 3 and 4 will activate the alarm output #3
Activation of both detection circuits at the same time will release circuit output #4 as well as activate the alarm
output #3
When either zone 1 or 2 is in alarm, output 1 will operate
When both zones 1 and 2 are in alarm at the same time, output #2 will operate
When either zone 3 or 4 is in alarm, output 3 will operate
When both zones 3 and 4 are in alarm at the same time, output #4 will operate
*Cross Zoning acceptable for NFPA 13, 15, and 16 type extinguishing systems.
PROGRAM #15
ZONES
SUP 1
SUP 2
#1
#2
#3
#4
OUTPUTS
Supervisory
Detection
Low Air Alarm
Detection
Low Air Alarm
#1 ALARM INDICATING
X
X
#2 RELEASE
XX
XX
#3 ALARM INDICATING
X
X
#4 RELEASE
XX
XX
XX = Cross-Zoned