Potter PFC-4410RC User Manual

Page 12

background image

12

PFC-4410RC • 5403550 • REV Q • 11/12

Backup Power Requirements

• PFC-4410RC - Standby 121 mA, alarm 274 mA at 24VDC, supervised

Service Use

NFPA 12 – Carbon Dioxide systems

NFPA 12A – Halon 1301 fire systems

NFPA 13 - Automatic Sprinkler

NFPA 15 - Water Spray Fixed System

NFPA 16 - Foam Water Sprinkler and Foam Water Spray

NFPA 17 - Dry Chemical

NFPA 17A - Wet Chemical

NFPA 72 - National Fire Alarm Code

• Local

• Remote Station (protected premise unit)

• Central Station (protected premise unit)

NFPA 750 - Water Mist

NFPA 2001 - Clean Agent Fire Extinguishing System

Listings and Approvals

PFC-4410RC - UL Standard 864, ULC Standard S527, FM, CSFM, NYMEA and CE Marked.

Terminals

• All terminals capable of #22 - #14 AWG wire

• All terminations have transient protection

• All four initiating device circuit terminals capable of handling linear heat detection.

Relay Outputs

• Common system alarm contacts SPDT rated 3 Amps, 30VDC resistive

• Common supervisory contacts SPST, N.O. rated 3 Amps, 30VDC resistive

• Common system trouble contacts SPDT rated 3 Amps, 30VDC resistive

• Common waterflow contacts, SPST, N.O. rated 3 Amps, 30VDC resistive

• Circuits connected to relays should be connected within the same room\

Auxiliary Power

• Auxiliary Power - 24VDC Special Application. Rated 200 mA max. Power limited, current limited, non-supervised

• Re-settable for 4-wire smoke detectors, see Annex A.

Annunciator Connection

• Auxiliary Power - 24VDC regulated. Rated 200 mA max. Power limited, current limited, supervised for RA-4410RC Annunciator

• RS-485 For connection to RA-4410RC remote annunciator
• Maximum 2000' with 22 AWG, 4000' with 20 AWG wire

Optional Accessories

CA2Z MODULE (Class A initiating device circuit):

Converts two Class B initiating device circuits to two Class A circuits.

CAM Module (Class A Notification Appliance Circuit):

Converts indicating appliance circuit from Class B to Class A. One model CAM (Class A Module) is required

for each circuit. (Do not use this on an output programmed as “Trouble Bell”.)

ARM-1/ARM-2 Module (Auxiliary Relay Module)

Activated by 24VDC Indicating and/or Releasing, polarity reversing circuits. The module provides a non-supervised DPDT Relay

that can be used for fan shutdown, door release, elevator recall, etc.

RA-4410RC (Remote Annunciator)

Connects to RS-485 & 24VDC terminals. Provides 34 LED’s for each zone in alarm supervisory, or trouble, each output activated

or in trouble, AC power, Power trouble, System trouble, Ground fault, Supervisory, Supervisory trouble, Alarm, Alarm silence and

Pre-discharge/Discharging.