Wire smoke detector compatibility data, Esl (max. no. of detectors per zone is 25), Hochiki (max. no. of detectors per zone is 25) – Potter PFC-4410RC User Manual
Page 89: Fenwal (max. no. of detectors per zone is 25), Potter (max. no. of detectors per zone is 25)

89
PFC-4410RC • 5403550 • REV Q • 11/12
2-Wire Smoke Detector Compatibility Data
Smoke Detector Compatibility Identifier "A"
System Sensor (Brk) (Max. No. Of Detectors Per Zone Is 20)
Det. Model
Identifier
Base Model
Identifier
1400*
A
N/A
N/A
2400*
A
N/A
N/A
2400TH*
A
N/A
N/A
2W-B
A
N/A
N/A
2WT-B
A
N/A
N/A
2WTR-B
A
N/A
N/A
Detection Systems (Max. No. Of Detectors Per Zone Is 25
)
Det. Model
Identifier
Base Model
Identifier
DS250
A
MB2W/MB2WL
A
DS250TH
A
MB2W/MB2WL
A
DS250HD
A
MB2W/MB2WL
A
Esl (Max. No. Of Detectors Per Zone Is 25)
Det. Model
Identifier
Base Model
Identifier
611U
S10
601U
S00
611UD
S10
601U
S00
611UT
S10
601U
S00
612U
S10
601U
S00
612UD
S10
601U
S00
613U5
S10
601U
S00
611UD
S10
609U10
S00
612UD
S10
609U10
S00
425C
S10
N/A
N/A
425CT
S10
N/A
N/A
Hochiki (Max. No. Of Detectors Per Zone Is 25)
Det. Model
Identifier
Base Model
Identifier
SLR-24*
HD-3
HSC-221R
HB-71
HSB-221
HB-54
HSB-221N
HB-54
NS6-221
NS4-221
NS6-220
HB-3
SLR-24H*
HD-3
HSC-221R
HB-71
HSB-221
HB-54
HSB-221N
HB-54
NS6-221
NS4-221
SIJ-24*
HD-3
HSC-221R
HB-71
HSB-221
HB-54
HSB-221N
HB-54
NS6-221
NS4-221
Fenwal (Max. No. Of Detectors Per Zone Is 25)
Det. Model
Identifier
Base Model Identifier
CPD-7051*
I51FE1
2-WIRE
FE51A
PSD-7155*
P55FE1
2WRLT
FE52A
PSD-7156*
P56FE1
2WRB
FE55A
All of the above Fenwal detectors and bases can be used in any combination
Retrofit Base Adaptor 70-501000-003, Identifier MAFE1 (for series 70-201000 Bases, Models -001, -002, -003 and -005)
Duct Housing with Detector Base DH-51, Identifier DH22FE5 (for CPD-7051 and PSD-7155 detectors only)
Potter (Max. No. Of Detectors Per Zone Is 25)
Det. Model
Identifier
Base Model
Identifier
PS-24* HD-3(HOCHIKI)
SB-46
HB-71(HOCHIKI)
HB-54(HOCHIKI)
SB-93
HB-3 (HOCHIKI
PS-24H HD-3(HOCHIKI)
SB-46
HB-71(HOCHIKI)
HB-54(HOCHIKI)
IS-24* HD-3(HOCHIKI)
SB-46
HB-71(HOCHIKI)
HB-54(HOCHIKI)
Only one detector can be supported in alarm per zone.
If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted.
Sync Module Compatibility - Panel is compatible with the following synchronization modules:
Amseco #SMD10-3A, Gentex #AVSM, System Sensor #MDL, Wheelock #DSM12/24
*UL and ULC Listed