Potter PFC-4410RC User Manual
Page 48
48
PFC-4410RC • 5403550 • REV Q • 11/12
QRS-ALARM ZONE
QRS
SUPERVISORY
ZONE
5.1K
EOLR
5.1K
EOLR
5.1K
EOLR
5.1K
EOLR
5.1K
EOLR
5.1K
AUX.
POWER
24VR DC
SUP 1/
ABORT
SUPV 2
ZONE 1
ZONE 2
ZONE 3
ZONE 4
DWG #3550-14
NO
COM
NC
NC
NO
NO
NO
COM
COM
COM
TROUBLE
SUPV
ALARM
SUPERVISORY
LOW AIR
VALVE TAMPER
WTRFL
ALARM CONDITION
SMOKE DET.
HEAT DET.
PULL STATION
WATERFLOW
WATERFLOW
TROUBLE CONDITION
PANEL PROBLEM
LOSS OF AC
LOSS OF BATTERY
WIRING PROBLEM
RELAY CONTACTS
DRY CONTACTS RATED AT 3A, 30VDC RESISTIVE
EOL
DIODE
ASSY
EOL
DIODE
ASSY
EOL
DIODE
ASSY
EOL
DIODE
ASSY
RE
D
RE
D
RE
D
RE
D
RE
D
BLAC
K
BLAC
K
BLAC
K
BLAC
K
BLAC
K
RELEASE
CIRCUIT
OUTPUT
4
RELEASE
CIRCUIT
OUTPUT
3
RELEASE
CIRCUIT
OUTPUT
2
RELEASE
CIRCUIT
OUTPUT
1
NON-POWER
LIMITED AND
SUPERVISED
12V BATT.
12V BATT.
PANEL OUTPUTS (INDICATING CIRCUITS)
BATT
POS
NEG
POS
NEG
BATTERY CABLE
OBSERVE POLARITY
RED +
BLACK -
PROGRAM
SWITCH
TO CIRCUIT BREAKER PANEL
120VAC/60Hz
165 VA MAX.
220VAC/50Hz
185 VA MAX.
NON-POWER
LIMITED AND
SUPERVISED
AC IN
CONNECTOR
24VNR DC RS-485
S
120 OHM
HOT - BLACK
NEUTRAL - WHITE
EARTH GROUND - GREEN
ZONE 1
ZONE 2
ZONE 3
ZONE 4
OUTPUT 1
OUTPUT 2
OUTPUT 3
OUTPUT 4
PROGRAM
MODE
RUN
MODE
AC POWER
POWER TBL
SYSTEM TBL
SUP TBL
GROUND
FAULT
SUP 1/ABORT
SUPERVISORY 2
COMMON ALARM
ALARM SILENCE
STEADY: DISCHARGING
FLASHING: PRE-
DISCHARGE
RUN
PROGRAM
SET
SELECT
FUNCTION
SCROLL-DOWN
BUZZER SILENCE
SIGNAL SILENCE
SYSTEM RESET
SCROLL-UP
BUZZER SILENCE
VIEWING ANGLE
RED OUTPUT LED STEADY: ABORT
N
120
See page 89 or label inside panel door for smoke detector
compatibility data.
See page 85 for battery information.
Wiring Diagram Program #14
4 Alarm Zones and 4 Release Circuits mapped 1 to 1.
2 Supervisory Zones
}
LAMP TEST
10. Maximum resistance on outputs is 10 ohms. Maximum
resistance on outputs programmed as releasing, is 1
divided by current requirements of solenoid.
11. Notification outputs do not provide synchronization.
If synchronization is needed, refer to the NAC table on
page 90. Synchronization is only on one circuit and not
betweeen circuits. The maximum cannot exceed 1 amp or
whatever the maximum that the sync' module can support,
whichever is lower.
NOTES:
1. Connect only UL Listed 24VDC devices to indicating
circuits.
2. Connect EOL Diode assembly IN SERIES with solenoid
on release circuit
3. Leave EOLR (provided) on all unused circuits.
4 Polarity is shown on indicating circuits in an activated
(off-normal) condition.
5. Polarity reverses when output is activated.
6. Maximum current per output is 1 Amp. Maximum voltage
is 33VDC.
7. Outputs identified as Release are Special Application. All
other outputs are Regulated 24 VDC, Rated 1 Amp each,
2.5 Amp total for all 4 circuits.
8. All initiating and NAC/Release circuits are supervised and
power limited. See note 3 on page 92 for power limited
wire routing instructions. All frequencies are continuous.
9. Refer to pgs. 16, 83-85 for installation, test and
maintenance information.
S
Initiating device
Notification appliance
Solenoid
End-of-Line diode assy
Legend