beautypg.com

Potter PFC-4410RC User Manual

Page 8

background image

8

PFC-4410RC • 5403550 • REV Q • 11/12

· Signal Silence button

· Buzzer Silence button

· Manual event scroll buttons

· Automatic resound of silenced trouble signals after 24 hours

· Built-in Trouble buzzer

· Common Contacts for Alarm/Trouble/Supervisory/Waterflow

· 32 Character Liquid Crystal Display (LCD)

· 34 LED display

· User Generated Banner Message

· User Generated Zone Labeling

· 24 or 90 hour Battery Standby available (Where required by FM and Others)

· 24 Hour Clock

· Password Protection

· Remote annunciator output

· 4-Wire resettable smoke detector power

Options See Appendix B of the manual for product data sheets.

1. CAM - Module to convert one Class B Indicating Appliance Circuit to one Class A circuit.

2. CA2Z - Module to convert two Class B Initiating Device Circuits to two Class A circuits.

3. ARM-1 - Module to provide non-supervised 4PDT Relay designed to be activated by 24VDC Indicating and/or Releasing,

polarity reversing circuits.

4. ARM-2 - Module to provide two Form C contacts activated by Indicating or Releasing, polarity reversing circuits.

5. ARM-44 - Module to provide 8 Form C contacts activated by corresponding initiating zones and outputs. Contact

manufacture for data sheet 5401202.

6. RA-4410RC – Remote annunciator provides 34 LED’s for each zone in alarm supervisory or trouble, each output activated

or in trouble, AC power, Power trouble, System trouble, Ground fault, Supervisory, Supervisory trouble, Alarm, Alarm

silence and Pre-discharge/Discharging. The annunciator also has a lamp test switch. Contact manufacture for data sheet

5401175.

7. Abort switch. Contact manufacture for data sheet 5401136.

8. RCDS-1 - Releasing Circuit Disable Switch Contact manufacture for data sheet 5401214.

Ordering Information

Model No.

Description

Stock No.

RA-4410RC

Remote annunciator

3006400

BB-RA-44R

Surface mount back box for RA-4410RC

3006401

EOLP-R

End of Line Plate f/Resistor

3002182

EOLP-D

End of Line Plate f/Diode Assy

3002181

P32-1T

Manual release station

1000447

Abort Switch

3001000

PFC-TW

Bezel for semi-flush mounting (white)

5090157

PFC-TR

Bezel for semi-flush mounting (red)

5090155

BT80

Battery, for 24 hour standby, 12V, 8.0AH (2 req’d)

5130084

BT120

Battery, for 60-90 hour standby, 12V, 12.0AH (2 req’d)

5130090

CA2Z

2-Zone Class A initiating module

3006013

CAM

Class A indicating circuit module

3005300

ARM-1

Auxiliary Relay Module 4 Pole

3004726

ARM-2

Auxiliary Relay Module

3004725

ARM-44

8 Relay Module

3006221

RCDS-1

Releasing Circuit Disable Switch

3001002

Spare or Replacement Parts

EOL Resistor

5080593

EOL Resistor and Diode Assembly for releasing circuit

3005012

EOL Resistor with 6" wire leads

3005013

eMatch Protection Assembly for eAEROSOL circuit

3005014

Main Circuit Board Module

3006230

This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference

to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules which

are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area

is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference.