Program #28 Mode

1. Apply power to panel.
2. Move the program switch down.
3. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.
4. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the SET

button to move to the next digit. After entering the third number the display will change.
(All panels are shipped with a 000 password.)
5. Press the FUNCTION (bottom) button until the display reads “PROGRAM #0”.
6. Press the SELECT button until the display reads “PROGRAM #28”.
7. Press the SET button.
8. Press the SELECT button to change the pre-discharge time.
9. Press the SET button to enter the pre-discharge time displayed.
10. Press the SELECT button to change the manual release pre-discharge time. See page 11 for abort selections.
11. Press the SET button to enter the manual release pre-discharge time selected.
12. Press the SELECT button to change the abort mode.
13. Press the SET button to enter the abort mode displayed.
14. The panel is completely programmed except for the custom banner and zone messages. Move the program switch back up.

Description:

Single Hazard, 3 detection zones, and a manual station zone

Inputs:

1 supervisory zone, 3 detection zones, 1 manual station zone, 1 abort circuit

Outputs:

2 general alarm, 1 eAEROSOL circuit, 1 supervisory

Operation:

Activation of either detection zones 1, 2, or 3 will activate the alarm output #1 and #2 and start the pre-

discharge timer for the eAEROSOL circuit output #3

Activation of the manual release zone #4 will activate the alarm outputs #1 and #2 and start the manual release

pre-discharge timer for eAEROSOL circuit output #3.

Activation of Supervisory 2 will activate output #4.

When either zone 1, 2, or 3 is in alarm, outputs #1 and #2 will operate and the pre-discharge timer for output #3

will start

When zone 4 is in alarm, outputs #1 and #2 will operate and the manual release pre-discharge timer for output

#3 will start.

PROGRAM #28

ZONES

SUPERVISORY 2

#1

#2

#3

#4

OUTPUTS

Supervisory

Detection

Detection

Detection

Manual Release

#1 ALARM INDICATING

X

X

X

X

#2 ALARM INDICATING

X

X

X

X

#3 eAEROSOL

X

X

X

X

#4 SUPERVISORY

X

SUP 1 defaults to abort