beautypg.com

Lamp test, Remote annunciator model ra-4410rc operation, Test procedure – Potter PFC-4410RC User Manual

Page 16: Test procedure (canada)

background image

16

PFC-4410RC • 5403550 • REV Q • 11/12

Lamp Test

When the panel is in a Normal Condition, pushing the two top buttons will illuminate all of the LED's and display for

approximately one second.

Remote Annunciator Model RA-4410RC Operation

Red LED’s:

Initiating Device Circuits Active (4)

Notification/Release Circuits Active (4)

Common Alarm (1)

Green LED’s: AC Power

Yellow LED’s: Initiating Device Circuits troubles (4)

Output Circuit Troubles (4)

Supervisory Initiating Zone (4)

Supervisory Bell Output Active (4)

(1) each: Sup 1/Abort, Supervisory 2, Power Trouble,

Supervisory Trouble, System Trouble, Ground Fault,

Pre-Discharge/Discharging, Alarm Silenced

The appropriate LED flashes to indicate a change of status on the panel. A trouble or supervisory condition will flash the appropriate

Yellow LED indicating the location of the condition. If any outputs are programmed as TROUBLE or SUPERVISORY BELL, that

Yellow output LED will flash indicating the output is activated. Pressing the BUZZER SILENCE button on the panel changes the

flashing zone Amber LED to steady on and turns the flashing Yellow output LED off.

An alarm condition will flash a Red LED indicating the zone in alarm and any outputs mapped to that zone that have activated.

Pressing the SIGNAL SILENCE button changes the flashing Red Zone LED to steady on and the flashing Red Output LED mapped

to that zone off unless the output is programmed as RELEASE. In addition, the Yellow ALARM/ SILENCE LED will light.

Any zone programmed as WATERFLOW is considered non-silenceable so the signal and buzzer silence buttons will have no

effect on the flashing zone and output LED's. A buzzer on the annunciator sounds for any trouble condition. When the panel

has a trouble or supervisory condition, pressing the SILENCE/LAMP TEST button silences the condition at the panel and all

annunciators. When no non-silenced trouble or supervisory conditions exist, pressing the SILENCE/LAMP TEST button can be

used to test the LED's.

The release panel supervises and communicates with the annunciator via separate connections for the RS-485 communication and

24VDC power requirements of the RA-4410RC. Separate cables should be used for power and communication. Shielded cable

shall be used for the communication line. Up to four annunciators can be connected to one panel. A rotary switch is provided on

the panel to indicate how many annunciators are connected. Another rotary switch is on the annunciator to set the address. The

annunciators must be addressed consecutively. See page 89 for wiring information. Refer to bulletin #8840024 for installation

instructions and maximum wire run.

Test Procedure

The system should be inspected, tested and maintained in accordance with NFPA-72 National Fire Alarm Code, Chapter 10 and

any other requirements of the local authority having jurisdiction.

Test Procedure (Canada)

The system should be inspected, tested and maintained in accordance with ULC Standard CAN/ULC-S536 and any other

requirements of the local authority having jurisdiction.

Testing should be done as a minimum as described below

1. Notify the fire department or other receiving station if alarm, supervisory and/or trouble signals are transmitted.

2. Notify the proper building personnel so that audible and/or visual signals can be ignored.

3. If the release panel is monitored by a building fire alarm panel, take appropriate action to eliminate any unwanted events.

4. Momentarily open each of the following circuits.

Each initiating device zone

Supervisory circuit

Notification Appliance/Releasing circuit - observe that this results in a trouble condition and all indicators operate as

described in the appropriate preceding section for the particular circuit that is faulted.

RED OUTPUT LED STEADY: ABORT

ZONE 1

ZONE 2

ZONE 3

ZONE 4

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

AC POWER

POWER TBL

SYSTEM TBL

SUP TBL

GROUND FAULT

SUP 1/ABORT

SUPERVISORY 2

COMMON ALARM

ALARM SILENCE

STEADY: DISCHARGING

FLASHING: PRE-DISCHARGE

LAMP TEST

SILENCE

DWG# 3550-17