Potter PFC-4410RC User Manual

Page 26

background image

26

PFC-4410RC • 5403550 • REV Q • 11/12

See page 89 or label inside panel door for smoke detector

compatibility data.

See page 85 for battery information.

Wiring Diagram Program #3

Dual Hazard, Combined Release - 2 Alarm Zones, 1 Manual

Station Zone, 1 Waterflow Zone, and 2 Supervisory Zones

OBSERVE POLARITY

WHEN CONNECTING

SMOKE DETECTORS

5.1K

EOLR

5.1K

EOLR

5.1K

EOLR

5.1K

EOLR

5.1K

EOLR

PS10A

LOW AIR

PS10A

VALVE

TAMPER

OSYSU

PCVS

EOLR

AUX.

POWER

24VR DC

SUP 1/

ABORT

SUPV 2

ZONE 1

HEAT OR

SMOKE

DETECTORS

ZONE 2

HEAT OR

SMOKE

DETECTORS

ZONE 3

WATERFLOW

SWITCH

PS10

ZONE 4

MANUAL

STATION

PANEL INPUTS (INITIATING ZONES)

CONNECT TO NORMALLY OPEN DEVICES

OR COMPATIBLE 2 WIRE SMOKE

DETECTORS.

MAXIMUM LINE RESISTANCE: 100 OHMS

(EXCEPT WITH LINEAR HEAT DETECTION)

OPTIONAL CA2Z MOUNTING LOCATION

EACH CA2Z WILL CONVERT

2 CLASS B ZONES INTO 2

CLASS A ZONES

OPTIONAL CLASS A

CONNECTIONS EOLR IS

NOT USED FOR CLASS A

DWG #3550-2

NO

COM

NC

NC

NO

NO

NO

COM

COM

COM

TROUBLE

SUPV

ALARM

SUPERVISORY

LOW AIR

VALVE TAMPER

WTRFL

ALARM CONDITION

SMOKE DET.

HEAT DET.

PULL STATION

WATERFLOW

WATERFLOW

TROUBLE CONDITION

PANEL PROBLEM

LOSS OF AC

LOSS OF BATTERY

WIRING PROBLEM

RELAY CONTACTS

DRY CONTACTS RATED AT 3A, 30VDC RESISTIVE

RED

RED

RED

RED

RED

BLACK

BLACK

BLAC

K

BLAC

K

BLACK

EOL

DIODE

ASSY

EOL

DIODE

ASSY

5.1K

EOLR

5.1K

EOLR

RELEASE

CIRCUIT

OUTPUT

4

RELEASE

CIRCUIT

OUTPUT

3

SUPV

BELL

OUTPUT

2

GENERAL

ALARM

BELL

OUTPUT

1

12V BATT.

12V BATT.

POS

NEG

POS

NEG

BATTERY CABLE

OBSERVE POLARITY

RED +

BLACK -

NON-POWER

LIMITED AND

SUPERVISED

BATT

PANEL OUTPUTS (INDICATING CIRCUITS)

PROGRAM

SWITCH

NON-POWER

LIMITED AND

SUPERVISED

AC IN

CONNECTOR

24 VNR DC

RS-485

120 OHM

TO CIRCUIT BREAKER PANEL

120VAC/60Hz

165 VA MAX.

220 VAC/50Hz

185 VA MAX.

HOT - BLACK
NEUTRAL - WHITE

EARTH GROUND - GREEN

ZONE 1

ZONE 2

ZONE 3

ZONE 4

OUTPUT 1

OUTPUT 2

OUTPUT 3

OUTPUT 4

PROGRAM

MODE

RUN

MODE

AC POWER

POWER TBL

SYSTEM TBL

SUP TBL
GROUND

FAULT

SUP 1/ABORT

SUPERVISORY 2

COMMON ALARM

ALARM SILENCE
STEADY: DISCHARGING

FLASHING: PRE-

DISCHARGE

RUN

PROGRAM

SET

SELECT

FUNCTION

SCROLL-DOWN

BUZZER SILENCE

SIGNAL SILENCE

SYSTEM RESET

SCROLL-UP

BUZZER SILENCE

VIEWING ANGLE

RED OUTPUT LED STEADY: ABORT

N

120

}

LAMP TEST

10. Maximum resistance on outputs is 10 ohms. Maximum

resistance on outputs programmed as releasing, is 1

divided by current requirements of solenoid.

11. Notification outputs do not provide synchronization.

If synchronization is needed, refer to the NAC table on

page 90. Synchronization is only on one circuit and not

betweeen circuits. The maximum cannot exceed 1 amp or

whatever the maximum that the sync' module can support,

whichever is lower.

NOTES:

1. Connect only UL Listed 24VDC devices to indicating

circuits.

2. Connect EOL Diode assembly IN SERIES with solenoid

on release circuit

3. Leave EOLR (provided) on all unused circuits.

4 Polarity is shown on indicating circuits in an activated

(off-normal) condition.

5. Polarity reverses when output is activated.

6. Maximum current per output is 1 Amp. Maximum voltage

is 33VDC.

7. Outputs identified as Release are Special Application. All

other outputs are Regulated 24 VDC, Rated 1 Amp each,

2.5 Amp total for all 4 circuits.

8. All initiating and NAC/Release circuits are supervised and

power limited. See note 3 on page 92 for power limited

wire routing instructions. All frequencies are continuous.

9. Refer to pgs. 16, 83-85 for installation, test and

maintenance information.

S

Initiating device

Notification appliance

Solenoid

End-of-Line diode assy

Legend