Potter PFC-4410RC User Manual
Page 35
35
PFC-4410RC • 5403550 • REV Q • 11/12
Program #7 Mode
1. Apply power to panel.
2. Move the program switch down.
3. Press the FUNCTION (bottom) button until the display reads “PASSWORD = 000”.
4. To enter a password, press the SELECT button until the proper number is displayed above the ^ symbol, then press the
SET button to move to the next digit. After entering the third number the display will change. (All panels are shipped with
a 000 password.)
5. Press the FUNCTION (bottom) button until the display reads “PROGRAM #0”.
6. Press the SELECT button until the display reads “PROGRAM #7”.
7. Press the SET button.
8. The panel is completely programmed except for the custom banner and zone messages. Move the program switch up.
Description: Single hazard, 2 zones and cross zoned with 2 supervisory zones.
Inputs:
2 detection zones (cross zoned), 1 waterflow zone, 1 low air zone, 2 supervisory zones
Outputs:
1 general alarm bell, 1 waterflow bell, 1 supervisory bell, 1 solenoid release circuit
Operation:
Activation of both detection zones at the same time will operate the solenoid release circuit and the general alarm bell.
Activation of either detection zone will operate the general alarm bell.
Activation of the waterflow zone will operate the waterflow bell.
Activation of either the low air zone or the supervisory zone will operate the supervisory bell.
When either zone 1 or 2 is in alarm - output #1 (general alarm) will operate.
When zones 1 and 2 are in alarm at the same time - output #4 (solenoid release) and output #1 (general alarm)
will operate.
When zone 3 is in alarm - output #2 (waterflow bell) will operate.
When either zone 4 or the supervisory zone is activated - output #3 (supervisory bell) will operate.
PROGRAM #7
ZONES
SUP 1
SUP 2
#1
#2
#3
#4
OUTPUTS
Supervisory
Detection
Detection
Waterflow
Low Air
Supervisory
#1 ALARM INDICATING
X
X
#2 ALARM INDICATING
X
#3 SUPERVISORY
X
X
X
#4 RELEASE
XX
XX
XX = Cross-Zoned