Potter PFC-4410RC User Manual
Page 20
20
PFC-4410RC • 5403550 • REV Q • 11/12
One Man Walktest
This display allows the user to select system mode NORMAL or ONE MAN WALKTEST by pressing the SELECT (middle)
button to toggle back and forth from NORMAL to ONE MAN WALKTEST. When the desired mode is displayed, press the SET
(top) button. If ONE MAN WALKTEST is selected for test purposes, the display must be restored to the NORMAL setting after
the test is completed by toggling to it using the SELECT (middle) button.
SET
After selecting NORMAL or ONE MAN WALKTEST, press the top button to set that mode.
SELECT
Press the middle button to toggle between NORMAL and CROSS ZONED.
FUNCTION
Press the bottom button to skip to the next function.
After selecting the operating mode or pressing the FUNCTION button a display similar to the following will appear in the display
window:
After 30 minutes of no activity the panel
automatically reverts to normal.
P R O G R A M
# 0
Note: NFPA 72, 2007, 6.12.5.2. requires a physical means of disconnecting release
circuits. The Potter Model, RCDS-1, complies with those requirements.