beautypg.com

Potter PFC-4410RC User Manual

Page 20

background image

20

PFC-4410RC • 5403550 • REV Q • 11/12

One Man Walktest

This display allows the user to select system mode NORMAL or ONE MAN WALKTEST by pressing the SELECT (middle)

button to toggle back and forth from NORMAL to ONE MAN WALKTEST. When the desired mode is displayed, press the SET

(top) button. If ONE MAN WALKTEST is selected for test purposes, the display must be restored to the NORMAL setting after

the test is completed by toggling to it using the SELECT (middle) button.

SET

After selecting NORMAL or ONE MAN WALKTEST, press the top button to set that mode.

SELECT

Press the middle button to toggle between NORMAL and CROSS ZONED.

FUNCTION

Press the bottom button to skip to the next function.

After selecting the operating mode or pressing the FUNCTION button a display similar to the following will appear in the display

window:

After 30 minutes of no activity the panel

automatically reverts to normal.

P R O G R A M

# 0

Note: NFPA 72, 2007, 6.12.5.2. requires a physical means of disconnecting release

circuits. The Potter Model, RCDS-1, complies with those requirements.