beautypg.com

Potter PFC-4410RC User Manual

Page 9

background image

9

PFC-4410RC • 5403550 • REV Q • 11/12

Specifications

PFC-4410RC

Type - 18 gauge sheet steel with hinged, removable, locked door

Size - 18 1/2" x 14 1/4" x 4 3/4"

Finish - Off-white or red cabinet with red on black logo.

Knockouts - 1/2" and 3/4", one of each on left side, two 3/4" and one 1/2" on right side, four 1/2", two 3/4" on top, and two 1/2"

and one 3/4" on the back

Option - Bezel for semi-flush mounting

PFC-4410RC Visual Indicators

LED Indicators (red = alarm)

32 Character Alpha-Numeric Liquid Crystal Display (LCD)

LCD

A 2 line 32 character alpha-numeric liquid crystal display shows the condition, status and circuit for all

Alarm, Supervisory and Trouble conditions.

CONDITION STATUS CIRCUIT

Alarm

Silenced

(Up To 10 Characters)

Trouble

Disabled

Output #1

Supervisory

Acknowledged

Output #2

Tamper

Output #3

Low Air

Output #4

High Air

Battery

Aborted

A.C.

Pre-discharging

Supervisory

Releasing

Zone #1

Released

Zone #2

Zone #3

Zone #4

Ground

PFC-4410RC Visual Indicators

In accordance with ULC S527-99 option B:

LED Annunciator Module

Red LED’s:

Initiating Device Circuits Active (4),

Notification/Release Circuits Active (4)

Common Alarm (1)

Green LED: AC Power

Yellow LED’s: Initiating Device Circuits Troubles (4),

Output Circuits Troubles (4)

Supervisory Initiating Zone (4)

Supervisory Bell Output Active (4)

(1) each: Supervisory 1, Supervisory 2, Power Trouble, Supervisory Trouble, System Trouble, Ground Fault,

Pre-Discharge/Discharging, Alarm Silenced

CONDITION

STATUS LED State

Trouble

Non-Silenced

Flashing

Trouble

Silenced

Steady ON

Alarm

Non-Silenced Flashing

Alarm

Silenced

Steady ON

Supervisory

Non-Silenced Flashing

Supervisory

Silenced Steady ON

Pre-discharge

Flashing

Discharging

Steady ON