EVCO EVCLC33DJ2 User Manual
Page 52

EVCO S.p.A.
Vcolor 338 L | Installer manual ver. 2.0 | Code 144VC338LE204
page 52 of 66
u2
0
600
ds (s/10)
120
air vent output inhibition duration from the conclusion of the brief
impulse for air vent opening and from the conclusion of the long
impulse for air vent closure (only if u1 = 1); see also u3 and u4
u3
0
600
ds (s/10)
10
duration of the brief impulse for air vent opening (only if u1 = 1);
see also u2 and u4
u4
0
600
ds (s/10)
30
duration of the long impulse for air vent closure (only if
u1 = 1); see also u2 and u3
PARAM.
MIN.
MAX.
U.M.
DEF.
SERIAL NETWORK
LA
1
247
- - -
247
device address
Lb
0
3
- - -
2
baud rate
0
=
2.400 baud
1
=
4.800 baud
2
=
9.600 baud
3
=
19.200 baud
LP
0
2
- - -
2
parity
0
=
none (no parity)
1
=
odd
2
=
even
PARAM.
MIN.
MAX.
U.M.
DEF.
ROTOR
k0
0
1
- - -
0
enables rotor
k1
0
1
- - -
1
door action on rotor: the door opening stops the rotation When the
door is closed afterwards,
0
=
the motor remains still
1
=
it restarts as before the interruption
k2
0
100
s
10
maximum motor activation duration. k2=0 immediately stops the
motor when opening the door.
k3
0
1
- - -
0
type of rack limit switch input contact
0
=
normally open (input active with closed contact)
1
=
normally closed (input active with open contact)
PARAM.
MIN.
MAX.
U.M.
DEF.
CLEANING
w0
0
500
°C/°F (2)
60
working set point for the precleaning phase