EVCO EVCLC33DJ2 User Manual
Page 49

EVCO S.p.A.
Vcolor 338 L | Installer manual ver. 2.0 | Code 144VC338LE204
page 49 of 66
t3
0
999
s
60
injection delay of the steam generated in direct mode from start of a
cooking cycle phase
t4
0
1
- - -
0
enabling of the restriction between the injection of the steam
generated in direct mode and the fan
1
= YES - the injection stops when the fan is off
If the fan is off when the steam has to be injected, the
injection will be made on the next fan switch-on and if the
fan has to stop during steam injection, it will be switched-
off after the conclusion of the injection
t5
0
1
- - -
0
enabling of the restriction between the injection of the steam
generated in direct mode and the output for temperature regulation.
1
=
YES - if the output is off when the steam is injected, the
injection will be made on successive output switch-on and if
the output has to stop during steam injection, it will be
switched-off after the conclusion of the injection
t6
t7
999
s
60
cycle time for injection of the steam generated with an external
humidifier
t7
0
t6
s
30
duration of the injection of the steam generated with external
humidifier corresponding to the maximum humidification
t8
0
999
s
60
injection delay of the steam generated with external humidifier from
start of a cooking cycle phase
t9
0
1
- - -
0
enabling of the restriction between the injection of the steam
generated with external humidifier and the fan
1
=
YES - if the fan is off when the steam has to be injected, the
injection will be made on successive fan switch-on and if the
fan has to stop during steam injection, it will be switched-off
on conclusion of the injection
t10
0
1
- - -
0
enabling of the restriction between the injection of the steam
generated with external humidifier and the output for temperature
regulation.
1
=
YES - if the output is off when the steam is injected, the
injection will be made on successive output switch-on and if
the output has to be closed during steam injection, it will be
switched-off on conclusion of the injection
t11
0
240
s
5
steam injection delay time from temperature regulation output
switch-on or from fan switch-on