EVCO EVCLC33DJ2 User Manual

Page 39

background image

EVCO S.p.A.

14

BOILER EXPANSION

14.1

Activation of the expansion

To enable the boiler expansion EVCLE305XXE

1.

Enable the boiler through parameter

2.

Set the steam generation mode with external or mixed

3.

Turn the device on

14.2

Electrical connection

14.3

Operation

14.3.1

Water charge management

When the device is ON, the water is charged and kept above

If the minimum required level is not reached within the expected time

activated.

If the maximum required level is not reached within the expected time

activated.

These alarms can be manually reset from

will be started.

14.3.2

Water heating management

When the device is ON, the water is heated and

cleaning the boiler or the room, the water is heated and

When water is not sufficient (minimum level not reac

14.3.3

Boiler rinse

It is possible to access the BOILER menu from the settings menu.

Vcolor 338 L | Installer manual ver. 2

page 39 of 66

pansion

EVCLE305XXE, it will be necessary to respect the following conditions.

Enable the boiler through parameter T15 (T15 = 1)

Set the steam generation mode with external or mixed humidification through parameter T0 (T0 = 1 o 2)

Electrical connection

ed and kept above the maximum level.

level is not reached within the expected time (parameter t27), the alarm “MIN

If the maximum required level is not reached within the expected time (parameter t28), the alarm “MAX BOILER WATER LEV”

key., pressing

the alarm will be reset and a new water

When the device is ON, the water is heated and maintained at “Boiler steam holding temperature” (paramet

cleaning the boiler or the room, the water is heated and maintained at “Boiler steam working temperature”

When water is not sufficient (minimum level not reached), the control is deactivated.

It is possible to access the BOILER menu from the settings menu.

| Installer manual ver. 2.0 | Code 144VC338LE204

T0 (T0 = 1 o 2)

MIN BOILER WATER LEV” will be

the alarm “MAX BOILER WATER LEV” will be

be reset and a new water charge cycle

” (parameter t18). While cooking,

at “Boiler steam working temperature” (parameter T17).