EVCO EVCLC33DJ2 User Manual
Page 39

EVCO S.p.A.
14
BOILER EXPANSION
14.1
Activation of the expansion
To enable the boiler expansion EVCLE305XXE
1.
Enable the boiler through parameter
2.
Set the steam generation mode with external or mixed
3.
Turn the device on
14.2
Electrical connection
14.3
Operation
14.3.1
Water charge management
When the device is ON, the water is charged and kept above
If the minimum required level is not reached within the expected time
activated.
If the maximum required level is not reached within the expected time
activated.
These alarms can be manually reset from
will be started.
14.3.2
Water heating management
When the device is ON, the water is heated and
cleaning the boiler or the room, the water is heated and
When water is not sufficient (minimum level not reac
14.3.3
Boiler rinse
It is possible to access the BOILER menu from the settings menu.
Vcolor 338 L | Installer manual ver. 2
page 39 of 66
pansion
EVCLE305XXE, it will be necessary to respect the following conditions.
Enable the boiler through parameter T15 (T15 = 1)
Set the steam generation mode with external or mixed humidification through parameter T0 (T0 = 1 o 2)
Electrical connection
ed and kept above the maximum level.
level is not reached within the expected time (parameter t27), the alarm “MIN
If the maximum required level is not reached within the expected time (parameter t28), the alarm “MAX BOILER WATER LEV”
key., pressing
the alarm will be reset and a new water
When the device is ON, the water is heated and maintained at “Boiler steam holding temperature” (paramet
cleaning the boiler or the room, the water is heated and maintained at “Boiler steam working temperature”
When water is not sufficient (minimum level not reached), the control is deactivated.
It is possible to access the BOILER menu from the settings menu.
| Installer manual ver. 2.0 | Code 144VC338LE204
T0 (T0 = 1 o 2)
MIN BOILER WATER LEV” will be
the alarm “MAX BOILER WATER LEV” will be
be reset and a new water charge cycle
” (parameter t18). While cooking,
at “Boiler steam working temperature” (parameter T17).