EVCO EVCLC33DJ2 User Manual
Page 48

EVCO S.p.A.
Vcolor 338 L | Installer manual ver. 2.0 | Code 144VC338LE204
page 48 of 66
PARAM.
MIN.
MAX.
U.M.
DEF.
FAN
F0
0
3
- - -
0
type of fan management
0
=
in “on/off” mode and at single speed
1
=
in “on/off” mode, with single speed and with inversion of the
direction of rotation of the fan
2
=
in “on/off” mode, with dual speed and with inversion of the
direction of rotation of the fan
3
=
in modulating mode and with inversion of the direction of
rotation of the fan
F1
5
120
s
15
duration of the fan switch-off due to the inversion of the direction of
rotation of the same (only if F0 = 1, 2 or 3); see also F2
F2
5
600
s
120
duration of the fan switch-on for every direction (only if F0 = 1, 2 or
3); see also F1
F3
0
1
- - -
0
temperature regulation output switch-off during fan switch-off due
to the effect of the inversion of the fan rotation direction (only if F0
= 1, 2 or 3)
0
= YES
F4
0
F5
%
0
minimum fan speed (intended as a percentage of the maximum
speed; only if F0 = 3)
F5
F4
100
%
100
maximum fan speed (intended as a percentage of the maximum
speed; only if F0 = 3)
F6
20/65
65/150
°C/°F (2)
60
temperature above which the technical compartment fan is
switched-on (referring to the temperature used by the control
module); see also F7
F7
1
99
°C/°F (2)
10
differential of F6
F8
0
100
%
10
Minimum speed that can be set by the fan user (intended as a
percentage of maximum speed; only if F0=3)
PARAM.
MIN.
MAX.
U.M.
DEF.
STEAM INJECTION
t0
0
2
- - -
0
steam generation mode
0
=
direct
1
=
with an external humidifier
2
=
combined (i.e. direct and with external humidifier)
t1
t2
999
s
60
cycle time for injection of the steam generated in direct mode
t2
0
t1
s
30
duration of the injection of the steam generated in direct mode
corresponding to the maximum humidification